Commissioning Record

Alarm configuration |
23
214
Deviation alarm supply temp zone 2
B No action 30min 10°C
215
Deviation alarm supply temp zone 3
B No action 30min 10°C
216
Freeze protection alarm zone 1
A
Fast stop
1s
217
Freeze protection alarm zone 2
A
Fast stop
1s
218
Freeze protection alarm zone 3
A
Fast stop
1s
219
Electric heater is overheated zone 1
A
Normal stop
1s
220
Electric heater is overheated zone 2
A
Normal stop
1s
221
Electric heater is overheated zone 3
A
Normal stop
1s
222
Sensor error supply air temp zone 1
B No action 5s
223
Sensor error supply air temp zone 2
B No action 5s
224
Sensor error supply air temp zone 3
B No action 5s
225
Sensor error room temp zone 1
B No action 5s
226
Sensor error room temp zone 2
B No action 5s
227
Sensor error room temp zone 3
B No action 5s
228
Sensor error extract temp zone 1
B No action 5s
229
Sensor error extract temp zone 2
B No action 5s
230
Sensor error extract temp zone 3
B No action 5s
231
Sensor error freeze protection zone 1
A
Fast stop
1s
162527 | A004