Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentSettings.S_DOSelect_ChangeOver1 X Holding Register (4x) 0563 RW MSV, 30563 1 Operation override Select changeOver 1 External
Modbus
0=Heating
1=Cooling
2=Auto
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_DOSelect_ChangeOver2 X Holding Register (4x) 0564 RW MSV, 30564 1 Operation override Select changeOver 2 External
(See signal list for DOSelect_ChangeOver1)
VentSettings.S_AirUnitAutoMode X Holding Register (4x) 0565 RW MSV, 30565 1 Operation override Running mode air handling unit:
Modbus
0=Off
1=Manual mode
2=Auto
3=Low speed
4=Normal speed
5=High speed
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_AirUnitManual X Holding Register (4x) 0566 RW MSV, 30566 1 Operation override Mode selection for air handling unit in running mode: manual mode
Modbus
0=Stop
1=Starting up
2=Low speed run
3=Normal speed run
4=High speed run
5=Heating support run
6=Cooling support run
7=CO₂ Run
8=Free cool run
9=Fan stop run
10=Fire run
11=Smoke run
12=Recirculation run
13=DeIcing run
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_SAFAutoMode X Holding Register (4x) 0567 RW MSV, 30567 1 Operation override Running mode supply air fan:
0=Off,
1=Manual output,
2=Auto,
3=Manual setpoint,
4=Low speed,
5=Normal speed,
6=High speed
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_SAFManualSetpoint
R
Holding Register (4x)
0568
RW
AV, 30568
10
P/Q
Operation override
Manual setpoint supply air fan if running mode: Manual setpoint
Page 28 of 45