Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentActual.A_AlaPt(143)
L
Input Status Register (1x)
0153
R
BV, 20153
Alarm point
Manual operation pretreatment
VentActual.A_AlaPt(144)
L
Input Status Register (1x)
0154
R
Alarm point
Sensor error outdoor air temperature
VentActual.A_AlaPt(145) L Input Status Register (1x) 0155 R Alarm point Sensor error intake air temperature
VentActual.A_AlaPt(146)
L
Input Status Register (1x)
0156
R
Alarm point
Sensor error supply air temperature
VentActual.A_AlaPt(147) L Input Status Register (1x) 0157 R Alarm point Sensor error exhaust air temperature
VentActual.A_AlaPt(148) L Input Status Register (1x) 0158 R Alarm point Sensor error extract air temperature
VentActual.A_AlaPt(149)
L
Input Status Register (1x)
0159
R
Alarm point
Sensor error room temperature 1
VentActual.A_AlaPt(150) L Input Status Register (1x) 0160 R Alarm point Sensor error room temperature 2
VentActual.A_AlaPt(151)
L
Input Status Register (1x)
0161
R
Alarm point
Sensor error room temperature 3
VentActual.A_AlaPt(152)
L
Input Status Register (1x)
0162
R
Alarm point
Sensor error room temperature 4
VentActual.A_AlaPt(153) L Input Status Register (1x) 0163 R Alarm point Sensor error pressure supply air
VentActual.A_AlaPt(154)
L
Input Status Register (1x)
0164
R
Alarm point
Sensor error pressure extract air
VentActual.A_AlaPt(155)
L
Input Status Register (1x)
0165
R
Alarm point
Sensor error flow supply air
VentActual.A_AlaPt(156) L Input Status Register (1x) 0166 R Alarm point Sensor error flow extract air
VentActual.A_AlaPt(157)
L
Input Status Register (1x)
0167
R
Alarm point
Sensor error flow exchanger supply air
VentActual.A_AlaPt(158)
L
Input Status Register (1x)
0168
R
Alarm point
Sensor error pressure exchanger extract air
VentActual.A_AlaPt(159) L Input Status Register (1x) 0169 R Alarm point Sensor error defrosting temperature
VentActual.A_AlaPt(160)
L
Input Status Register (1x)
0170
R
Alarm point
Sensor error freeze protection temperature 1
VentActual.A_AlaPt(161) L Input Status Register (1x) 0171 R Alarm point Sensor error freeze protection temperature 2
VentActual.A_AlaPt(162) L Input Status Register (1x) 0172 R Alarm point Sensor error freeze protection temperature 3
VentActual.A_AlaPt(163)
L
Input Status Register (1x)
0173
R
Alarm point
Sensor error CO2 room/extract air
VentActual.A_AlaPt(164) L Input Status Register (1x) 0174 R Alarm point Sensor error humidity room/extract air
VentActual.A_AlaPt(165)
L
Input Status Register (1x)
0175
R
Alarm point
Sensor error humidity supply air
VentActual.A_AlaPt(166)
L
Input Status Register (1x)
0176
R
Alarm point
Sensor error extra controller
VentActual.A_AlaPt(167) L Input Status Register (1x) 0177 R Alarm point Signal error external control supply air fan
VentActual.A_AlaPt(168)
L
Input Status Register (1x)
0178
R
Alarm point
Signal error external control extract air fan
VentActual.A_AlaPt(169)
L
Input Status Register (1x)
0179
R
Alarm point
Sensor error humidity outdoor
VentActual.A_AlaPt(170) L Input Status Register (1x) 0180 R Alarm point Sensor error extra sensor 1
VentActual.A_AlaPt(171)
L
Input Status Register (1x)
0181
R
Alarm point
Sensor error extra sensor 2
VentActual.A_AlaPt(172) L Input Status Register (1x) 0182 R Alarm point Sensor error extra sensor 3
VentActual.A_AlaPt(173) L Input Status Register (1x) 0183 R Alarm point Sensor error extra sensor 4
VentActual.A_AlaPt(174)
L
Input Status Register (1x)
0184
R
Alarm point
Sensor error extra sensor 5
VentActual.A_AlaPt(175) L Input Status Register (1x) 0185 R Alarm point Sensor error external temperature setpoint
VentActual.A_AlaPt(176)
L
Input Status Register (1x)
0186
R
Alarm point
Signal error external flow setpoint
VentActual.A_AlaPt(177)
L
Input Status Register (1x)
0187
R
Alarm point
Sensor error pressure filter supply air
VentActual.A_AlaPt(178) L Input Status Register (1x) 0188 R Alarm point Sensor error pressure filter extract air
VentActual.A_AlaPt(179)
L
Input Status Register (1x)
0189
R
Alarm point
Sensor error efficiency temperature exchanger
VentActual.A_AlaPt(180)
L
Input Status Register (1x)
0190
R
BV, 20190
Alarm point
Fault communication device
VentActual.A_AlaPt(181) L Input Status Register (1x) 0191 R BV, 20191 Alarm point Malfunction Extra Controller
VentActual.A_AlaPt(182)
L
Input Status Register (1x)
0192
R
BV, 20192
Alarm point
Internal error
VentActual.A_AlaPt(183)
L
Input Status Register (1x)
0193
R
BV, 20193
Alarm point
Smoke detector service
VentActual.A_AlaPt(184) L Input Status Register (1x) 0194 R BV, 20194 Alarm point Smoke detector connection error
VentActual.A_AlaPt(185)
L
Input Status Register (1x)
0195
R
BV, 20195
Alarm point
Malfunction preheater
4.1-1-00
VentActual.A_AlaPt(186) L Input Status Register (1x) 0196 R Alarm point Communication fault BMS master 4.1-1-00
VentActual.A_AlaPt(187) L Input Status Register (1x) 0197 R BV, 20197 Alarm point Leakage heater valve 4.1-1-00
VentActual.A_AlaPt(188)
L
Input Status Register (1x)
0198
R
BV, 20198
Alarm point
Sensor error preheater temperature
4.1-1-00
VentActual.A_AlaPt(189) L Input Status Register (1x) 0199 R BV, 20199 Alarm point Malfunction supply air fan 6 4.3-1-00
VentActual.A_AlaPt(191)
L
Input Status Register (1x)
0200
R
BV, 20200
Alarm point
Malfunction supply air fan 7
4.3-1-00
VentActual.A_AlaPt(192)
L
Input Status Register (1x)
0201
R
BV, 20201
Alarm point
Malfunction supply air fan 8
4.3-1-00
Page 42 of 45