ccess V4.X Configuration manual
13 (56) 2018-07-11
Flow transmitter
DESCRIPTION

󰇟

󰇠
󰇟󰇠
󰇟󰇠


,5

,

Flow transmitter supply air
K-factor
X-factor Default 0,5
Flow transmitter extract air
K-factor
X-factor Default 0,5
Exchanger supply air pressure sensor
K-factor
X-factor Default 0.96…0.98
Operation settings: Data & Settings > Fan control
Sequence Configure types
Activate/configure: Configuration > Function Configuration > Function Activation
10 different sequence
Sequence Heating Cooling Start
Heating
Start
Cooling
Sequence name
Sequence-A 2 Off 0% 0% Heating
Sequence-B 1 1 0% 0% Exchanger
Sequence-C Off 2 0% 0% Cooling
Sequence-D Off Off 0% 0% Recirculation 1
Sequence-E Off Off 0% 0% Recirculation 2
Sequence-F Off Off 0% 0% Fan heating/cooling
Sequence-G Off Off 0% 0% Heating 2
Sequence-H Off Off 0% 0% Cooling 2
Sequence-I Off Off 0% 0% Exchanger extract
Sequence-J Off Off 0% 0% Extra heating/cooling capacity
Menu function Value Comments
Step controller 1 > (Sub menu for step controller 1 settings) Visible only if Heater electric
and/or cooler DX are configure
Step controller 2 > (Sub menu for step controller 2 settings) Visible only if Heater electric
and/or cooler DX are configure
Heating sequence step to start at 100%
when normal start
Step 1
Full heating when outdoor temperature is
below
3 °C
Heating sequence step to start at 100%
when heating start
Step 2
Description on heating sequence ('B' column 'Heating') and cooling sequence ('C'
column 'Cooling'). See example below.
Start Heating and Start cooling ('D' column 'Start Heating' and 'E' column 'Start
Cooling') it starts before (-x%) or after (+x%) of the control signal.