Commissioning Record
Table Of Contents
Function settings
|
9
Function
Default setting Set value
If water heater
Pump control
□ None
□ Auto
□ Always running
None
Auto
Always running
Pump stop delay
5 min
min
Pump running when outdoor temp. is
below:
10 °C
°
Hysteresis to allow pump stop
1 °C
°
Freeze protection
□ No
□ Yes
No
Yes
Alarm limit when unit is running
7 °C
°
P-band when unit is running
5 °C
°
Set point when unit is stopped
20 °C
°
Cooling
Type of cooler
□ None
□ Water
□ DX
None
Water
DX
Type of feedback, cooler
□ None
□ Alarm
□ Run indication
None
Alarm
Run indication
If water cooler
Pump control
□ None
□ Auto
□ Always running
None
Auto
Always running
Pump stop delay
5 min
min
If DX cooler
Reduction of min limit supply air temp
5 °C
°
Type of step control □ Sequential
□ Binary
Sequential
Binary
Number of steps
□ 1
□ 2
1
2
162527 | A004