Contents 1 2 3 4 5 About this document........................................1 How to set up a function ...................................1 2.1 Login ...................................................1 2.2 Activation.............................................1 2.3 Configuration ........................................1 2.4 Allocation .............................................1 2.5 Operation settings ..................................1 How to use the configuration wizard....................2 3.
About this document | 1 About this document This document describes how to setup functions in your Access controller and contains quick configuration guides for the most common functions. All available functionality is described in detail in the “Access 4x configuration manual” available on the online catalogue or Systemair Configurator for products using the Access control platform.
2 | How to use the configuration wizard 3 How to use the configuration wizard The configuration wizard is a menu that simplify the procedure to Activate and Configure common accessories and functions and Allocate it’s in- and outputs. The wizard makes necessary configurations automatically and guide the user through limited options. Access the configuration wizard via in the navigation bar or via the configuration menu.
How to use the configuration wizard | 3.1.3 Allocation Configuration > Configuration wizard > Set up “function” > In-/Outputs Confirm the in-/output allocation of the connected signals and sensors. Configure in-/output settings (sensor measuring range, polarity, edit name of sensor/signal etc.) as necessary. Complete the setup by pressing Confirm In-/Outputs and complete setup. Configuration > ...
4 | Save commissioning settings 4 Save commissioning settings When the installation is complete and all functions are tested it is recommended to save a local backup of the current configuration in the control unit. Select Yes on Save commissioning settings in the Configuration > System settings > Save and restore settings menu. Overview: Configuration > System settings > Save and restore settings 24 Jun 10:31 Save commissioning settings Yes Step by step: 1.
Quick configuration guides | Note: Default Unit name is either Systemair controller or the unit model name, for example Topvex TR03 HW CAV. 5.1.2 I/O naming Change the name of an I/O (in-/outputs), for example a temperature sensor, by selecting the desired I/O function in the Configuration > I/O allocation settings sub menus and changing the menu row Name.
6 | Quick configuration guides 1. Select Configuration from the navigation icons 2. Select Functions 3. Select Function activation 4. Select Heating/Cooling sequence setup 5. Select the sequence to rename (e.g Cooling 2) 6. Edit the name of the sequence by selecting Name. 5.1.4 Alarm naming How to edit alarm names is described in chapter 5.2. 5.2 Alarm configuration Configure any alarm available in the controller in the Configuration > Alarms menu. Overview: Configuration > ...
Quick configuration guides | 1. Select Configuration from the navigation icons 2. Select Functions 3. Select Function activation 4. Select Pressure as Fan control type. 5.3.2 Allocation Setup differential pressure sensors. Select I/O (in-/output) placement for where the differential pressure sensors are connected. Set the sensors’ signal and corresponding measuring range in the Configuration > I/O allocation settings > Analog inputs menu.
8 | Quick configuration guides 5.3.3 Operation settings Adjust the fan pressure set points in the Data & Settings > Fan Control > Fan setpoints menu. Overview: Data & Settings > Fan control > Fan setpoints 24 Jun 10:31 Setpoint low speed supply air fan 100 Pa Setpoint low speed extract air fan 100 Pa Setpoint normal speed supply air fan 200 Pa Setpoint normal speed extract air fan 200 Pa Setpoint high speed supply air fan 200 Pa Setpoint high speed extract air fan 200 Pa Step by step: 1.
Quick configuration guides | 5.4.2 Configuration Configure the number of connected room temperature sensors in the Configuration > Functions > Temperature control menu. Overview: Configuration > Functions > Temperature control 24 Jun 10:31 2 Room temperature sensor Average Calculation mode room temperature Step by step: 1. Select Configuration from the navigation icons 2. Select Functions 3. Select Temperature control 4. Select number of connected Room temperature sensors 5.
10 | Quick configuration guides 5.4.4 Operation settings Data & Settings > Temp Control > Supply air controller 24 Jun 10:31 Min limit supply air 14.0 °C Max limit supply air 30.0 °C Step by step: 1. Select Data & Settings from the navigation icons 2. Select Temperature control 3. Select Room controller 4. Adjust Setpoint room to the desired temperature setpoint 5. Go back to Temperature control (use the navigation path Data & Settings > Temperature control) 6. Select Supply air controller 7.
Quick configuration guides | 1. Select Configuration from the navigation icons 2. Select Functions 3. Select Extended operation 4. Select Yes for desired extended operation fan speeds 5.5.
12 | Quick configuration guides 5.6 Fan compensation 5.6.1 Activation Select Yes for Fan Compensation in the Configuration > Functions > Function activation menu. Overview: Configuration > Functions > Function activation 24 Jun 10:31 Fan compensation curves Yes Step by step: 1. Select Configuration from the navigation icons 2. Select Functions 3. Select Function activation 4. Set Yes on Fan compensation curves 5.6.
Quick configuration guides | Step by step: 1. Select Configuration from the navigation icons 2. Select Functions 3. Select Fan compensation curve 1/2/3 4. Select which fan level(s) the compensation curve should apply to as Fan level 5. Select when the compensation curve is active as Mode 6. Select which fan the compensation curve applies to as Fan 7. Select which of the available sensors to use for compensation. 5.6.
14 | Quick configuration guides 5.7 Air quality control (Fan start/stop) 5.7.1 Activation Activate the Fan start/stop function for Air quality control from the list of available functions in the Configuration > Functions > Function activation menu. Overview: Configuration > Functions > Function activation Air quality control 24 Jun 10:31 Fan start/stop function Step by step: 1. Select Configuration from the navigation icons 2. Select Functions 3. Select Function activation 4.
Quick configuration guides | 5.7.3 Allocation Select I/O (in-output) placement for where the CO2 sensor is connected to the controller in the Configuration > I/ O allocation settings > Analog inputs menu. Overview: Configuration > I/O allocation settings > Analog inputs 24 Jun 10:31 Analog inputs Device CO2 room/extract air Controller Configuration > ... > Analog inputs > CO2 room/extract air Position UI3 24 Jun 10:31 Min volt input (Vmin) 0.0 V Man volt input (Vmax) 10.
16 | Quick configuration guides 5.7.4 Operating settings Adjust CO2 limits for the Fan start/stop function and adjust the minimum run time for CO2 control in the Data & Settings > Demand control > Air quality control menu. Overview: Data & Settings > Demand control > Air quality control 24 Jun 10:31 Start limit fan start/stop CO2 800 ppm Stop hysteresis fan start/stop CO2 160 ppm 20 min Min time for CO2 control Step by step: Note: Setpoint CO2 not active for this configuration.
Quick configuration guides | 5.8.2 Configuration Configure the operation of the air handling unit, outdoor/exhaust air dampers, the fan setpoints and fire damper function when Fire alarm in the Configuration > Functions > Fire/Smoke > Fire function submenus. Overview: Configuration > ...
18 | Quick configuration guides 5.8.3 Allocation Select I/O (in-/output) placement of where fire alarm activation input, fire damper output and position feedback input are connected to the controller in the Configuration > I/O allocation settings submenus Digital inputs and Digital outputs.
Quick configuration guides | 5.8.4 Operation settings Set up the Fire damper test settings in the Data & Settings > Fire/Smoke menu. Note: Only applicable if fire damper test is configured. Overview: Data & Settings > Fire/Smoke 24 Jun 10:31 90 s Run time fire damper 7 days Test interval fire damper 15 Test hour fire damper Step by step: 1. Select Data & Settings from the navigation icons 2. Select Fire/Smoke 3. Set max allowed fire damper run time as Run time fire damper 4.
20 | Quick configuration guides 5.9.2 Operation settings Set up all operation parameters for the free cooling function in the Data & Settings > Demand control > Free cooling menu.
Quick configuration guides | 5.10 External cooler (DX) 5.10.1 Activation Select and activate an unused cooling sequence (C, H or J) in the Configuration > Functions > Function activation > Heating/Cooling sequence setup menu. Overview: Configuration > ... > ...
22 | Quick configuration guides 5.10.2 Configuration Configure what type of cooler is connected in the Configuration > Functions > Function activation > Heating/Cooling sequence setup > Cooling menu. Overview: Configuration >. .. > Heating/Cooling sequence setup > Cooling 24 Jun 10:31 Cooling Type of sequence Type of cooler DX Type of feedback Alarm Digital start output Yes Run indication from DX-compressor Yes Step by step: 1. Select Configuration from the navigation icons 2.
Quick configuration guides | Configuration >... > Analog outputs > Cooling (SEQ-C) 24 Jun 10:31 Range output Configuration > I/O allocation settings > Digital outputs 0–10 V 24 Jun 10:31 Digital outputs Device Cooling start (SEQ-C) Controller Position DO4 Step by step: 1. Select Configuration from the navigation icons 2. Select I/O allocation settings 3. Select Digital inputs 4. Select the input connected to the cooler’s feedback contact (e.g. UI4) as position for Feedback cooling (SEQ-C) 5.
24 | Quick configuration guides 5.10.4 Operation settings Adjust the start/stop point for the digital output: Cooling start (SEQ-C) in the Data & Settings > Temperature control > Cooling menu.
Quick configuration guides | 5.11 External heater (Water) 5.11.1 Activation Select and activate an unused heating sequence (A, G or J) in the Configuration > Functions > Function activation > Heating/Cooling sequence setup menu. Overview: Configuration > ... > ...
26 | Quick configuration guides 5.11.2 Configuration Configure what type of heater that is connected (e.g. water) and additional functions such as freeze protection and pump control in the Configuration > Functions > Function activation > Heating/Cooling sequence setup > Heating menu. Overview: Configuration > ...
Quick configuration guides | 5.11.3 Allocation Select I/O (in-output) placement of where the heater control signal output, pump start output and pump feedback input are connected to the controller in the Configuration > I/O allocation settings submenus Digital inputs, Analog outputs and Digital outputs.
28 | Quick configuration guides 5.11.4 Operation settings Adjust the settings for pump control and freeze protection in the Data & Settings > Temperature control > Heating menu Overview: Data & Settings > Temperature control > Heating 24 Jun 10:31 Pump stop delay 5 min Pump-kick hour 15 h Pump running when outdoor temperature < 10 °C Hysteresis to allow pump stop 1 °C > Freeze protection 1 Data & Settings > ...
Quick configuration guides | 5.12 Changeover Note: To get a start signal for heating or cooling, use the corresponding sequence’s digital start signal, see chapter 5.10.2. 5.12.1 Configuration Select one heating sequence and one cooling sequence out of the configured sequences to use with the changeover function in the Configuration > Functions > Function activation > Heating/Cooling sequence setup > Changeover settings menu. Overview: Configuration > ...
30 | Quick configuration guides Configuration > ... > Analog outputs > Changeover 1 24 Jun 10:31 Range output 0-10 V Step by step: 1. Select Configuration from the navigation icons 2. Select I/O allocation settings 3. Select Digital inputs 4. Select the input connected to the heating/cooling feedback (e.g. DI4) as position for Cooling/(Heating) changeover 1 5. Go back to I/O allocation settings (use the navigation path Configuration > I/O allocation settings) 6. Select Analog outputs 7.
Quick configuration guides | 5.13.2 Allocation Select the I/O (in-output) placement of where the external stop switch is connected to the controller in the Configuration > I/O allocation settings > Digital inputs menu. Overview: Configuration > I/O allocation settings > Digital inputs 24 Jun 10:31 Digital inputs Device External stop Controller Position DI6 Step by step: 1. Select Configuration from the navigation icons 2. Select I/O allocation settings 3. Select Digital inputs 4.
32 | Quick configuration guides 5.14.2 Operating settings Adjust the start/stop limits for support heating/cooling and the min run time for the support control function in the Data & Settings > Demand control > Support control menu.