| Quick configuration guides
4.12 Change over
4.12.1 Configuration
Select one heating sequence and one cooling sequence out of the configured sequences to use with the changeover
function in the Configuration > Functions > Function activation > Heating/Cooling sequence setup >
Changeover settings menu.
Overview:
Configuration > ... > Heating/Cooling sequence setup >
Changeover settings
04 Apr 13:54
Changeover 1
Changeover sequence for heating Heating
Changeover sequence for cooling Cooling
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Heating/Cooling sequence setup
5. Select Changeover settings
6. Select which sequence to control the changeover function when heating as Changeover sequence for heating
7. Select which sequence to control the changeover function when cooling as Changeover sequence for cooling.
4.12.2 Allocation
Select I/O (in-output) placement of where the changeover output and feedback input are connected to the controller in
the Configuration > I/O allocation settings submenus Digital inputs, Analog outputs and Digital
outputs.
Overview:
Configuration > I/O allocation settings > Digital
inputs
04 Apr 13:54
Digital inputs
Device Position
Cooling/(Heating) changeover 1
Controller
DI4
Configuration > I/O allocation settings > Analog
outputs
04 Apr 13:54
Analog outputs
Device Position
Changeover 1
Controller AO4
Configuration > ... > Analog outputs > Changeover 1
04 Apr 13:54
Range output
0-10 V
157618 | A002