Commissioning Record
Table Of Contents
Function settings
|
11
Function
Default setting
Set value
Support control
⊠ No
□ Yes
No
Yes
Start heating room temperature 15 °C °
Stop heating room temperature
21 °C
°
Start cooling room temperature
30 °C
°
Stop cooling room temperature
28 °C
°
Preheater
⊠ No
□ Yes
No
Yes
Start/Stop function
⊠ Unit running
□ When defrosting
Unit running
When defrosting
Preheater setpoint:
-15 °C
°
Exchanger defrosting mode (only
applied for SC, TC units without section
defrosting)
⊠ Pressure monitoring Pressure monitoring
Bypass ⊠ On
□ Off
On
Off
Stop defrosting
⊠ On
□ Off
On
Off
Outdoor temp. to allow defrosting
18 °C
°
Outdoor temp. for stop of supply air fan
18 °C
°
Max deviation exchanger pressure to
start defrosting
50%
%
Pressure hysteresis to end defrosting
60%
%
Exchanger defrosting mode (only
applied for SC, TC units with section
defrosting)
⊠ Section defrosting Section defrosting
Allow fan stop defrosting if exchanger
pressure > max limit
⊠ Yes
□ No
Yes
No
Max allowed deviation exchanger
pressure when defrosting
150%
%
Max deviation exchanger pressure to
start defrosting
25%
%
Pressure hysteresis to end defrosting
60%
%
Setpoint temperature min limit
4 °C
°
Temperature hysteresis to end
defrosting
4 °C
°
Calibration extract air flow
_____________
Calibration exchanger pressure
_____________
162527 | A004