- 5.4 Temperature control type (Room)
- 5.5 Extended operation
- 5.6 Fan compensation
- 5.7 Air quality control (Fan start/stop)
- 5.8 Fire/Smoke function (Fire)
- 5.9 Free cooling
- 5.10 External cooler (DX)
- 5.11 External heater (Water)
- 5.12 Changeover
- 5.13 External stop
- 5.14 Support control
Quick configuration guides |
13
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Fan compensation curve 1/2/3
4. Select which fan level(s) the compensation curve should apply to as Fan level
5. Select when the compensation curve is active as Mode
6. Select which fan the compensation curve applies to as Fan
7. Select which of the available sensors to use for compensation.
5.6.3 Operation settings
Set up fan setpoint compensation values and sensor input values for the curve points in the Data & Settings > Fan
control > Fan compensation curves menu.
Overview:
Data & Settings > Fan control > Fan compensation curves
24 Jun 10:31
Fan compensation curve 1
>
Fan compensation curve 2
>
Fan compensation curve 3
>
Data & Settings > ... > Fan compensation curves > Fan
compensation curve 2
24 Jun 10:31
Compensation curve
Sensor
value
Compensation
Lowest sensor value
15.0 °C
0.0 Pa
Middle sensor value
20.0 °C
0.0 Pa
Highest sensor value
25.0 °C
0.0 Pa
Step by step:
1.
Select Data & Settings from the navigation icons
2. Select Fan control
3. Select Fan compensation curves
4. Select Fan compensation curve 1/2/3
5. Set up Lowest sensor value
a. Set the lowest sensor value for compensation as Sensor value
b. Set the desired fan setpoint compensation at that sensor value as Compensation
6. Set up Middle sensor value
a. Set a middle sensor value for compensation as Sensor value
b. Set the desired fan setpoint compensation at that sensor value as Compensation
7. Set up Highest sensor value
a. Set the highest sensor value for compensation as Sensor value
b. Set the desired fan setpoint compensation at that sensor value as Compensation
157618 | A008