QUICK CONFIGURATION GUIDE ACCESS SW 4 0 1 04 TO 4 6 1 00 157618A008
Table Of Contents
- 1 About this document
- 2 How to set up a function
- 3 How to use the configuration wizard
- 4 Save commissioning settings
- 5 Quick configuration guides
- 5.1 Editable naming
- 5.2 Alarm configuration
- 5.3 Fan control type (Pressure)
- 5.4 Temperature control type (Room)
- 5.5 Extended operation
- 5.6 Fan compensation
- 5.7 Air quality control (Fan start/stop)
- 5.8 Fire/Smoke function (Fire)
- 5.9 Free cooling
- 5.10 External cooler (DX)
- 5.11 External heater (Water)
- 5.12 Changeover
- 5.13 External stop
- 5.14 Support control
Quick configuration guides |
15
5.7.3 Allocation
Select I/O (in-output) placement for where the CO2 sensor is connected to the controller in the Configuration > I/
O allocation settings > Analog inputs menu.
Overview:
Configuration > I/O allocation settings > Analog
inputs
24 Jun 10:31
Analog inputs
Device Position
CO2 room/extract air Controller
UI3
Configuration > ... > Analog inputs > CO2 room/extract air 24 Jun 10:31
Min volt input (Vmin)
0.0 V
Man volt input (Vmax)
10.0 V
Sensor value at Vmin 0.0
Sensor value at Vmax
2000.0
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Analog inputs
4. Select the input connected to the sensor (e.g. UI3) as position for CO2 room/extract air
5. Select CO2 room/extract air
6. Set Sensor value at Vmin the same as the start point of the sensor’s selected measuring range
7. Set Sensor value at Vmax the same as the end point of the sensor’s selected measuring range
8. Set Min volt input (Vmin) and Max volt input (Vmax) to values corresponding to the sensor’s signal type (e.
g. 0…10 V, 2…10 V etc.)
157618 | A008