5.8.2 Configuration
Configure the operation of the air handling unit, outdoor/exhaust air dampers, the fan setpoints and fire damper func-
tion when Fire alarm in the Configuration > Functions > Fire/Smoke > Fire function submenus.
Overview:
Configuration > ... > Fire/Smoke > Fire function 24 Jun 10:31
Operation mode when fire alarm
Continuous run
Supply air fan setpoint type when fire alarm Manual output
Manual output
75%
Extract air fan setpoint type when fire alarm Manual output
Manual output
75%
Outdoor air damper function when fire alarm
Normal function (follow the
fan)
Exhaust air damper function when fire alarm
Normal function (follow the
fan)
Configuration > ... > Fire function > Fire damper
24 Jun 10:31
Mode Not active
Test No test
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Fire/Smoke
4. Select Fire function
5. Select desired air handling unit’s operation when fire alarm as Mode
6. Select desired fan setpoint type as Supply air fan setpoint type when fire alarm
7. Select desired fan setpoint type as Extract air fan setpoint type when fire alarm
8. If either Manual setpoint or Manual output was selected set the desired value in the corresponding menu row
now visible
9. Select the operation of the outdoor/exhaust air damper when fire alarm as Outdoor/Exhaust air damper when
fire alarm
10.Select Fire damper
11.Select the normal position of the fire dampers or if fire damper function should not be used as Mode
12.Select if and how the fire dampers shall be tested as Test.
157618 | A008