QUICK CONFIGURATION GUIDE ACCESS SW 4 0 1 04 TO 4 6 1 00 157618A008
Table Of Contents
- 1 About this document
- 2 How to set up a function
- 3 How to use the configuration wizard
- 4 Save commissioning settings
- 5 Quick configuration guides
- 5.1 Editable naming
- 5.2 Alarm configuration
- 5.3 Fan control type (Pressure)
- 5.4 Temperature control type (Room)
- 5.5 Extended operation
- 5.6 Fan compensation
- 5.7 Air quality control (Fan start/stop)
- 5.8 Fire/Smoke function (Fire)
- 5.9 Free cooling
- 5.10 External cooler (DX)
- 5.11 External heater (Water)
- 5.12 Changeover
- 5.13 External stop
- 5.14 Support control
26
| Quick configuration guides
5.11.2 Configuration
Configure what type of heater that is connected (e.g. water) and additional functions such as freeze protection and
pump control in the Configuration > Functions > Function activation > Heating/Cooling sequence
setup > Heating menu.
Overview:
Configuration > ... > Heating/Cooling sequence setup >
Heating
24 Jun 10:31
Type of sequence Heating
Type of heater
Water
Type of freeze protection
Temperature sensor
Freeze protection sensor
Freeze protection
temperature 1
Airflow reduction during active freeze protection
No
Pump control
Yes
Pump running mode
Auto
Type of feedback
Alarm
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Heating/Cooling sequence setup
5. Select Heating (SEQ-A)
6. Select Water as Type of heater
7. Select Temperature sensor as Type of freeze protection
8. Select an unused sensor (e.g. 1) as Freeze protection temperature sensor
9. Optional, select Yes as Airflow reduction during active freeze protection
10.Select Yes as Pump control
11.Select the desired type of pump control (e.g. Auto) as Pump running mode
12.Select the desired type of pump feedback (e.g. Alarm) as Type of feedback.
157618 | A008