ACCESS QUICK CONFIG GUIDE SW 4 0 1 05 157618
Table Of Contents
- 1 About this document
- 2 How to set up a function
- 3 Save commissioning settings
- 4 Quick configuration guides
- 4.1 Editable naming
- 4.2 Alarm configuration
- 4.3 Fan control type (Pressure)
- 4.4 Temperature control type (Room)
- 4.5 Extended operation
- 4.6 Fan compensation
- 4.7 CO2 control (Fan start/stop)
- 4.8 Fire/Smoke function (Fire)
- 4.9 Free cooling
- 4.10 External cooler (DX)
- 4.11 External heater (Water)
- 4.12 Change over
- 4.13 External stop
- 4.14 Support control
Quick configuration guides |
25
4.11.2 Configuration
Configure what type of heater that is connected (e.g. water) and additional functions such as freeze protection and
pump control in the Configuration > Functions > Function activation > Heating/Cooling sequence
setup > Heating menu.
Overview:
Configuration > ... > Heating/Cooling sequence setup >
Heating
04 Apr 13:54
Type of sequence Heating
Type of heater
Water
Type of freeze protection
Temperature sensor
Freeze protection sensor
Freeze protection
temperature 1
Pump control
Yes
Pump running mode
Auto
Type of feedback
Alarm
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Heating/Cooling sequence setup
5. Select Heating (SEQ-A)
6. Select Water as Type of heater
7. Select Temperature sensor as Type of freeze protection
8. Select an unused sensor (e.g. 1) as Freeze protection temperature sensor
9. Select Yes as Pump control
10.Select the desired type of pump control (e.g. Auto) as Pump running mode
11.Select the desired type of pump feedback (e.g. Alarm) as Type of feedback.
157618 | A002