ACCESS QUICK CONFIG GUIDE SW 4 0 1 05 157618

22
| Quick configuration guides
Configuration > I/O allocation settings > Digital
outputs
04 Apr 13:54
Digital outputs
Device Position
Cooling start (SEQ-C)
Controller DO4
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Digital inputs
4. Select the input connected to the cooler’s feedback contact (e.g. UI4) as position for Feedback cooling (SEQ-C)
5. Go back to I/O allocation settings (use the navigation path Configuration > I/O allocation
settings)
6. Select Analog outputs
7. Select the analog output connected to the cooler control signal (e.g. AO4) as position for Cooling (SEQ-C)
8. Select Cooling (SEQ-C)
9. Adjust Range output to fit with the signal range of the external cooler (e.g. 2-10 V)
10.Go back to I/O allocation settings (use the navigation path Configuration > I/O allocation
settings)
11.Select Digital outputs
12.Select the digital output connected to the cooler (e.g. DO4) as position for Cooling start (SEQ-C).