Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentSettings.S_FanComp2X3
R
Holding Register (4x)
0825
RW
AV, 30825
10
Fan compensation curve
Curve 2 point 3 sensor value
VentSettings.S_FanComp2Y3
R
Holding Register (4x)
0826
RW
AV, 30826
10
Fan compensation curve
Curve 2 point 3 setpoint compensation
VentSettings.S_FanComp3X1 R Holding Register (4x) 0827 RW AV, 30827 10 Fan compensation curve Curve 3 point 1 sensor value
VentSettings.S_FanComp3Y1
R
Holding Register (4x)
0828
RW
AV, 30828
10
Fan compensation curve
Curve 3 point 1 setpoint compensation
VentSettings.S_FanComp3X2 R Holding Register (4x) 0829 RW AV, 30829 10 Fan compensation curve Curve 3 point 2 sensor value
VentSettings.S_FanComp3Y2 R Holding Register (4x) 0830 RW AV, 30830 10 Fan compensation curve Curve 3 point 2 setpoint compensation
VentSettings.S_FanComp3X3
R
Holding Register (4x)
0831
RW
AV, 30831
10
Fan compensation curve
Curve 3 point 3 sensor value
VentSettings.S_FanComp3Y3 R Holding Register (4x) 0832 RW AV, 30832 10 Fan compensation curve Curve 3 point 3 setpoint compensation
VentSettings.S_NeutralZone
R
Holding Register (4x)
0833
RW
AV, 30833
10
T
Temperature setting
Neutral zone around supply setpoint before heating and cooling.
VentSettings.S_FreeCoolSAFOffset
R
Holding Register (4x)
0834
RW
AV, 30834
P/Q
Free cooling
Setpoint offset supply air fan if free cooling
4.3-1-00
VentSettings.S_FreeCoolEAFOffset R Holding Register (4x) 0835 RW AV, 30835 1 P/Q Free cooling Setpoint offset extract air fan if free cooling 4.3-1-00
VentSettings.S_FilterGuard1Limit_X2 R Holding Register (4x) 0838 RW AV, 30838 1 Q Alarm setting Supply air filter, filter air flow (reference point for calculation of alarm
limit)
4.6-1-00
VentSettings.S_FilterGuard1Limit_Y2 R Holding Register (4x) 0839 RW AV, 30839 10 P Alarm setting Supply air filter, final pressure drop at filter air flow (reference point for
calculation of alarm limit)
4.6-1-00
VentSettings.S_FilterGuard2Limit_X2 R Holding Register (4x) 0842 RW AV, 30842 1 Q Alarm setting Extract air filter, filter air flow (reference point for calculation of alarm
limit)
4.6-1-00
VentSettings.S_FilterGuard2Limit_Y2 R Holding Register (4x) 0843 RW AV, 30843 10 P Alarm setting Extract air filter, final pressure drop at filter air flow (reference point for
calculation of alarm limit)
4.6-1-00
VentSettings.S_SummerModeSupplySetpoint R Holding Register (4x) 0844 RW AV, 30844 10 T Summer setting Supply air temp setpoint at summer time
VentSettings.S_SummerModeOutdoortemp
R
Holding Register (4x)
0845
RW
AV, 30845
10
T
Summer setting
Outdoor temp for switching between summer and winter mode
VentSettings.S_SummerModeStartDate X Holding Register (4x) 0846 RW 1 Summer setting Date for start of summer period
VentSettings.S_SummerModeStartMonth
X
Holding Register (4x)
0847
RW
Summer setting
Month for start of summer period
VentSettings.S_SummerModeStopDate
X
Holding Register (4x)
0848
RW
Summer setting
Date for stop of summer period
VentSettings.S_SummerModeStopMonth X Holding Register (4x) 0849 RW 1 Summer setting Month for stop of summer period
VentActual.A_BMS_OutDoorTemp
R
Holding Register (4x)
0850
RW
AV, 30850
10
T
AI function
Outdoor temperature sent from BMS system
4.1-1-00
VentSettings.S_EnergyHeaterLeakagedT
R
Holding Register (4x)
0851
RW
AV, 30851
10
T
Energy insight
Alarm limit in delta T, for leakage heater valve
4.1-1-00
VentSettings.S_Zone1SetP(0) R Holding Register (4x) 0852 RW AV, 30852 10 T Temperature setting Setpoint zone 1 air temperature 4.3-1-00
VentSettings.S_Zone2SetP
R
Holding Register (4x)
0853
RW
AV, 30853
10
T
Temperature setting
Setpoint zone 2 air temperature
4.3-1-00
VentSettings.S_Zone3SetP R Holding Register (4x) 0854 RW AV, 30854 10 T Temperature setting Setpoint zone 3 air temperature 4.3-1-00
VentSettings.S_Zone1SetpointMax(0) R Holding Register (4x) 0855 RW AV, 30855 10 T Temperature setting Max limit of zone 1 supply setpoint if cascade control 4.3-1-00
VentSettings.S_Zone1SetpointMin(0)
R
Holding Register (4x)
0856
RW
AV, 30856
10
T
Temperature setting
Min limit of zone 1 supply setpoint if cascade control
4.3-1-00
VentSettings.S_Zone2SetpointMax R Holding Register (4x) 0857 RW AV, 30857 10 T Temperature setting Max limit of zone 2 supply setpoint if cascade control 4.3-1-00
VentSettings.S_Zone2SetpointMin
R
Holding Register (4x)
0858
RW
AV, 30858
10
T
Temperature setting
Min limit of zone 2 supply setpoint if cascade control
4.3-1-00
VentSettings.S_Zone3SetpointMax
R
Holding Register (4x)
0859
RW
AV, 30859
10
T
Temperature setting
Max limit of zone 3 supply setpoint if cascade control
4.3-1-00
VentSettings.S_Zone3SetpointMin R Holding Register (4x) 0860 RW AV, 30860 10 T Temperature setting Min limit of zone 3 supply setpoint if cascade control 4.3-1-00
VentSettings.S_Zone1NeutralZone(0) R Holding Register (4x) 0861 RW AV, 30861 10 T Temperature setting Neutral zone around supply setpoint before heating and cooling zone 1. 4.3-1-00
VentSettings.S_Zone2NeutralZone R Holding Register (4x) 0862 RW AV, 30862 10 T Temperature setting Neutral zone around supply setpoint before heating and cooling zone 2. 4.3-1-00
VentSettings.S_Zone3NeutralZone R Holding Register (4x) 0863 RW AV, 30863 10 T Temperature setting Neutral zone around supply setpoint before heating and cooling zone 3. 4.3-1-00
VentSettings.S_FrostProtSPRunZone1
R
Holding Register (4x)
0864
RW
AV, 30864
10
T
Alarm setting
Alarm limit freeze protection alarm zone 1
4.3-1-00
VentSettings.S_FrostProtSPStopZone1 R Holding Register (4x) 0865 RW AV, 30865 10 T Unit setting Setpoint freeze protection zone 1 if standby mode 4.3-1-00
VentSettings.S_FrostProtPGainZone1 R Holding Register (4x) 0866 RW AV, 30866 10 T Unit setting P-band freeze protection zone 1 if running mode
(setpoint=alarm limit+P-band)
4.3-1-00
VentSettings.S_FrostProtSPRunZone2 R Holding Register (4x) 0867 RW AV, 30867 10 T Alarm setting Alarm limit freeze protection alarm zone 2 4.3-1-00
VentSettings.S_FrostProtSPStopZone2
R
Holding Register (4x)
0868
RW
AV, 30868
10
T
Unit setting
Setpoint freeze protection zone 2 if standby mode
4.3-1-00
Page 37 of 45