Configuration Manual

Version Document
A
001
A
ccess V4.X Configuration manual
28 (56) 2018-07-11
Fan compensation curve 1, 2, 3
Speed
All speeds
Only low speed
Only normal speed
Only high speed
Low and normal speed
Normal and high speed
Select the fan steps were the compensation shall be active
Mode
Off
In all modes
Only when defrosting
Fan
Supply air fan and extract air fan
Supply air fan only
Extract air fan only
Sensor
“Temperature sensor”
“Pressure sensor”
CO2 sensor
RH sensor
All active temperature sensors and differential pressure sensors will be included in
the "scroll list" for selectable sensors
Operation settings: Data & Settings > Fan control > Fan compensation
Settings to set up the compensation curve
Fan compensation curve 1, 2, 3
Low point
Input value break point for selected sensor
Compensation compensation value (negative or positive adjustment)
Middle point
Input value break point for selected sensor
Compensation compensation value (negative or positive adjustment)
High point
Input value break point for selected sensor
Compensation compensation value (negative or positive adjustment)
Support control
Activate Configuration > Function Configuration > Function Activation
Support control
No
Yes
Configure Configuration > Function Configuration > Support control
Enable support control when ventilation unit is shut down
No
Yes