ACCESS QUICK CONFIG GUIDE SW 4 0 1 05 157618
Table Of Contents
- 1 About this document
- 2 How to set up a function
- 3 Save commissioning settings
- 4 Quick configuration guides
- 4.1 Editable naming
- 4.2 Alarm configuration
- 4.3 Fan control type (Pressure)
- 4.4 Temperature control type (Room)
- 4.5 Extended operation
- 4.6 Fan compensation
- 4.7 CO2 control (Fan start/stop)
- 4.8 Fire/Smoke function (Fire)
- 4.9 Free cooling
- 4.10 External cooler (DX)
- 4.11 External heater (Water)
- 4.12 Change over
- 4.13 External stop
- 4.14 Support control
8
| Quick configuration guides
4.4.3 Allocation
Select I/O (in-/output) placement for where the room temperature sensors are connected to the controller in the Con-
figuration > I/O allocation settings > Analog inputs menu.
Overview:
Configuration > I/O allocation settings > Analog
inputs
04 Apr 13:54
Analog inputs
Device Position
Room temperature 1
Controller Select I/O
Room temperature 2
Controller Select I/O
Room temperature 3
Controller Select I/O
Room temperature 4
Controller Select I/O
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Analog inputs
4. Select the input connected to the sensor (e.g. UI1) as position for Room temperature 1/2/3/4
5. Repeat step 4 for any remaining room temperature sensors.
4.4.4 Operation settings
Adjust the room temperature setpoint in the Data & Settings > Temperature control > Room controller
menu.
Adjust limits for the supply air controller in the Data & Settings > Temperature control > Supply air con-
troller menu.
Overview:
Data & Settings > Temperature Control > Room
controller
04 Apr 13:54
Setpoint room
22.0 °C
Data & Settings > Temp Control > Supply air
controller
04 Apr 13:54
Min limit supply air
14.0 °C
Max limit supply air
30.0 °C
157618 | A002