| Quick configuration guides
4.5.3 Allocation
Select I/O (in-/output) placement for the extended operation speeds in the Configuration >I/O allocation set-
tings > Digital inputs menu
Overview:
Configuration > I/O allocation settings > Digital
inputs
04 Apr 13:54
Digital inputs
Device Position
Extended operation low speed
Controller Select I/O
Extended operation normal speed
Controller DI4
Extended operation high speed
Controller Select I/O
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Digital inputs
4. Select the input of the extended operation (e.g. DI4) as position for Extended operation low speed, Extended
operation normal speed, Extended operation high speed
5. Repeat step 4 for any remaining extended operation speeds.
4.5.4 Operation settings
Adjust extended operation time to the desired stop delay in the Time settings menu.
Overview:
Time settings
04 Apr 13:54
Extended operation stop delay 0 min
Step by step:
1.
Select Time settings from the navigation icons
2. Set the desired stop delay as Extended operation stop delay