Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
AlaData.Ala_MalfunctionHeatingZone2_DelayValue
I
Holding Register (4x)
0494
RW
sec
Alarm setting
Alarm delay malfunction heating zone 2
4.3-1-00
AlaData.Ala_MalfunctionHeatingZone3_DelayValue
I
Holding Register (4x)
0495
RW
sec
Alarm setting
Alarm delay malfunction heating zone 3
4.3-1-00
AlaData.Ala_MalfunctionCoolingZone1_DelayValue I Holding Register (4x) 0496 RW 1 sec Alarm setting Alarm delay malfunction cooling zone 1 4.3-1-00
AlaData.Ala_MalfunctionCoolingZone2_DelayValue
I
Holding Register (4x)
0497
RW
sec
Alarm setting
Alarm delay malfunction cooling zone 2
4.3-1-00
AlaData.Ala_MalfunctionCoolingZone3_DelayValue I Holding Register (4x) 0498 RW 1 sec Alarm setting Alarm delay malfunction cooling zone 3 4.3-1-00
AlaData.Ala_ControlErrorSupplyTempZone1_DelayValue I Holding Register (4x) 0499 RW 1 min Alarm setting Alarm delay deviation alarm supply temperature zone 1 4.3-1-00
AlaData.Ala_ControlErrorSupplyTempZone2_DelayValue
I
Holding Register (4x)
0500
RW
min
Alarm setting
Alarm delay deviation alarm supply temperature zone 2
4.3-1-00
AlaData.Ala_ControlErrorSupplyTempZone3_DelayValue I Holding Register (4x) 0501 RW 1 min Alarm setting Alarm delay deviation alarm supply temperature zone 3 4.3-1-00
AlaData.Ala_LowTempFrostGuardZone1_DelayValue
I
Holding Register (4x)
0502
RW
sec
Alarm setting
Alarm delay freeze protection alarm zone 1
4.3-1-00
AlaData.Ala_LowTempFrostGuardZone2_DelayValue
I
Holding Register (4x)
0503
RW
sec
Alarm setting
Alarm delay freeze protection alarm zone 2
4.3-1-00
AlaData.Ala_LowTempFrostGuardZone3_DelayValue I Holding Register (4x) 0504 RW 1 sec Alarm setting Alarm delay freeze protection alarm zone 3 4.3-1-00
AlaData.Ala_ElectricOverheatZone1_DelayValue
I
Holding Register (4x)
0505
RW
sec
Alarm setting
Alarm delay electric heater is overheated zone 1
4.3-1-00
AlaData.Ala_ElectricOverheatZone2_DelayValue
I
Holding Register (4x)
0506
RW
sec
Alarm setting
Alarm delay electric heater is overheated zone 2
4.3-1-00
AlaData.Ala_ElectricOverheatZone3_DelayValue I Holding Register (4x) 0507 RW 1 sec Alarm setting Alarm delay electric heater is overheated zone 3 4.3-1-00
AlaData.Ala_SensorErrorTempSupplyZone1_DelayValue
I
Holding Register (4x)
0508
RW
sec
Alarm setting
Alarm delay sensor error supply air temp zone 1
4.3-1-00
AlaData.Ala_SensorErrorTempSupplyZone2_DelayValue
I
Holding Register (4x)
0509
RW
sec
Alarm setting
Alarm delay sensor error supply air temp zone 2
4.3-1-00
AlaData.Ala_SensorErrorTempSupplyZone3_DelayValue I Holding Register (4x) 0510 RW 1 sec Alarm setting Alarm delay sensor error supply air temp zone 3 4.3-1-00
AlaData.Ala_SensorErrorTempRoomZone1_DelayValue
I
Holding Register (4x)
0511
RW
sec
Alarm setting
Alarm delay sensor error room temp zone 1
4.3-1-00
AlaData.Ala_SensorErrorTempRoomZone2_DelayValue I Holding Register (4x) 0512 RW 1 sec Alarm setting Alarm delay sensor error room temp zone 2 4.3-1-00
AlaData.Ala_SensorErrorTempRoomZone3_DelayValue I Holding Register (4x) 0513 RW 1 sec Alarm setting Alarm delay sensor error room temp zone 3 4.3-1-00
AlaData.Ala_SensorErrorTempExtractZone1_DelayValue
I
Holding Register (4x)
0514
RW
sec
Alarm setting
Alarm delay sensor error extract temp zone 1
4.3-1-00
AlaData.Ala_SensorErrorTempExtractZone2_DelayValue I Holding Register (4x) 0515 RW 1 sec Alarm setting Alarm delay sensor error extract temp zone 2 4.3-1-00
AlaData.Ala_SensorErrorTempExtractZone3_DelayValue
I
Holding Register (4x)
0516
RW
sec
Alarm setting
Alarm delay sensor error extract temp zone 3
4.3-1-00
AlaData.Ala_SensorErrorTempFrostZone1_DelayValue
I
Holding Register (4x)
0517
RW
sec
Alarm setting
Alarm delay sensor error freeze protection zone 1
4.3-1-00
AlaData.Ala_SensorErrorTempFrostZone2_DelayValue I Holding Register (4x) 0518 RW 1 sec Alarm setting Alarm delay sensor error freeze protection zone 2 4.3-1-00
AlaData.Ala_SensorErrorTempFrostZone3_DelayValue
I
Holding Register (4x)
0519
RW
sec
Alarm setting
Alarm delay sensor error freeze protection zone 3
4.3-1-00
AlaData.Ala_SignalErrorFeedbackCoolerValve_DelayValue
I
Holding Register (4x)
0520
RW
sec
Alarm setting
Alarm delay signal error feedback cooler valve
4.5-1-00
AlaData.Ala_SignalErrorFeedbackOutdoorDamper_DelayValue I Holding Register (4x) 0521 RW 1 sec Alarm setting Alarm delay signal error feedback outdoor air damper 4.5-1-00
AlaData.Ala_SignalErrorFeedbackRecircDamper_DelayValue
I
Holding Register (4x)
0522
RW
sec
Alarm setting
Alarm delay signal error feedback recirculation damper
4.5-1-00
AlaData.Ala_DeviceWarning_DelayValue I Holding Register (4x) 0523 RW 1 sec Alarm setting Alarm delay device warning 4.4-1-00
AlaData.Ala_DeviceAlarm_DelayValue I Holding Register (4x) 0524 RW 1 sec Alarm setting Alarm delay device alarm 4.4-1-00
AlaData.Ala_EATROverpressure_DelayValue
I
Holding Register (4x)
0525
RW
sec
Alarm setting
Alarm delay high pressure EATR
4.5-1-00
AlaData.Ala_SensorErrorEATR_DelayValue I Holding Register (4x) 0526 RW 1 sec Alarm setting Alarm delay sensor error pressure EATR 4.5-1-00
AlaData.Ala_FailSafe_DelayValue
I
Holding Register (4x)
0527
RW
sec
Alarm setting
Alarm delay fail-safe airflow/temperature control
4.6-1-00
AlaData.Ala_FilterGuard3_DelayValue
I
Holding Register (4x)
0528
RW
sec
Alarm setting
Alarm delay pre-filter alarm supply air
4.6-1-00
AlaData.Ala_FilterGuard4_DelayValue I Holding Register (4x) 0529 RW 1 sec Alarm setting Alarm delay end-filter alarm supply air 4.6-1-00
AlaData.Ala_FilterGuard5_DelayValue
I
Holding Register (4x)
0530
RW
sec
Alarm setting
Alarm delay pre-filter alarm extract air
4.6-1-00
AlaData.Ala_SensorErrorFilterGuard3_DelayValue
I
Holding Register (4x)
0531
RW
sec
Alarm setting
Alarm delay sensor error pressure pre-filter supply air
4.6-1-00
AlaData.Ala_SensorErrorFilterGuard4_DelayValue I Holding Register (4x) 0532 RW 1 sec Alarm setting Alarm delay sensor error pressure end-filter supply air 4.6-1-00
AlaData.Ala_SensorErrorFilterGuard5_DelayValue
I
Holding Register (4x)
0533
RW
sec
Alarm setting
Alarm delay sensor error pressure pre-filter extract air
4.6-1-00
VentSettings.S_AirFlowK(10) R Holding Register (4x) 0537 RW AV, 30537 10 Flow calculation K-constant for calculating air flow: SAF pressure
airflow = S_AirFlowK * A_AI_SAFPressure^S_AirFlowx
VentSettings.S_AirFlowX(10)
R
Holding Register (4x)
0538
RW
AV, 30538
100
Flow calculation
X-constant for calculating air flow: SAF pressure
VentSettings.S_AirFlowK(11) R Holding Register (4x) 0539 RW AV, 30539 10 Flow calculation K-constant for calculating air flow: EAF pressure
VentSettings.S_AirFlowX(11)
R
Holding Register (4x)
0540
RW
AV, 30540
100
Flow calculation
X-constant for calculating air flow: EAF pressure
VentSettings.S_AirFlowK(12)
R
Holding Register (4x)
0541
RW
AV, 30541
10
Flow calculation
K-constant for calculating air flow: Supply air flow
VentSettings.S_AirFlowX(12) R Holding Register (4x) 0542 RW AV, 30542 100 Flow calculation X-constant for calculating air flow: Supply air flow
VentSettings.S_AirFlowK(13)
R
Holding Register (4x)
0543
RW
AV, 30543
10
Flow calculation
K-constant for calculating air flow: Extract air flow
Page 26 of 45