ACCESS QUICK CONFIG GUIDE SW 4 0 1 05 157618

6
| Quick configuration guides
Configuration > ... > Analog inputs > Pressure supply
air
04 Apr 13:54
Min volt input (Vmin)
0.0 V
Max volt input (Vmax)
10.0 V
Sensor value at Vmin 0.0
Sensor value at Vmax
500.0
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Analog inputs
4. Select the input connected to the sensor (e.g. UI2) as position for Pressure supply air
5. Select the input connected to the sensor (e.g UI1) as position for Pressure extract air
6. Select Pressure supply air
7. Set Sensor at Vmin the same as the start point of the sensor’s selected measuring range
8. Set Sensor at Vmax the same as the end point of the sensor’s selected measuring range
9. Set Min volt input (Vmin) and Max volt input (Vmax) to values corresponding to the sensor’s signal type (e.
g. 0…10V, 2…10V etc.)
10.Go back to Analog inputs (use the navigation path Configuration > I/O allocation settings > Analog
inputs)
11.Select Pressure extract air and repeat steps 7 through 9.
4.3.3 Operation settings
Adjust the fan pressure set points in the Data & Settings > Fan Control > Fan setpoints menu.
Overview:
Data & Settings > Fan control > Fan setpoints
04 Apr 13:54
Setpoint low speed supply air fan 100 Pa
Setpoint low speed extract air fan 100 Pa
Setpoint normal speed supply air fan 200 Pa
Setpoint normal speed extract air fan 200 Pa
Setpoint high speed supply air fan
200 Pa
Setpoint high speed extract air fan 200 Pa
Step by step:
1.
Select Data & Settings from the navigation icons
2. Select Fan control
3. Select Fan setpoints
4. Select and adjust setpoints for the available fan speed levels.
157618 | A002