4.7.3 Allocation
Select I/O (in-output) placement for where the CO2 sensor is connected to the controller in the Configuration > I/
O allocation settings > Analog inputs menu.
Overview:
Configuration > I/O allocation settings > Analog
inputs
04 Apr 13:54
Analog inputs
Device Position
CO2 room/extract air Controller
UI3
Configuration > ... > Analog inputs > CO2 room/extract air 04 Apr 13:54
Min volt input (Vmin)
0.0 V
Man volt input (Vmax)
10.0 V
Sensor value at Vmin 0.0
Sensor value at Vmax
2000.0
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Analog inputs
4. Select the input connected to the sensor (e.g. UI3) as position for CO2 room/extract air
5. Select CO2 room/extract air
6. Set Sensor value at Vmin the same as the start point of the sensor’s selected measuring range
7. Set Sensor value at Vmax the same as the end point of the sensor’s selected measuring range
8. Set Min volt input (Vmin) and Max volt input (Vmax) to values corresponding to the sensor’s signal type (e.
g. 0…10 V, 2…10 V etc.)