ACCESS QUICK CONFIG GUIDE SW 4 0 1 05 157618

20
| Quick configuration guides
4.10 External cooler (DX)
4.10.1 Activation
Select and activate an unused cooling sequence (C, H or J) in the Configuration > Functions > Function acti-
vation > Heating/Cooling sequence setup menu.
Overview:
Configuration > ... > ... > Heating/Cooling sequence
setup
04 Apr 13:54
Position
Heating Cooling
Start
Heating
Start
Cooling
Name
SEQ-C
Off
2 0 % 0 %
Cooling
>
SEQ-H
Off
3 0 % 0 %
Cooling 2
>
SEQ-J
Off Off
0 % 0 %
External
heating/cooling
capacity
>
Note:
Off = Sequence not activated. Sequence with lower number activates before sequence with higher number.
In software version 4.0–1–05 the term “Off” is replaced with “No”.
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Heating/Cooling sequence setup
5. 5. Assign the activation order for the cooling sequence by selecting number (1-10) in column Cooling for
SEQ-C, -H or -J
157618 | A002