Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentSettings.S_AirFlowX(13)
R
Holding Register (4x)
0544
RW
AV, 30544
100
Flow calculation
X-constant for calculating air flow: Extract air flow
VentSettings.S_AirFlowK(14)
R
Holding Register (4x)
0545
RW
AV, 30545
10
Flow calculation
K-constant for calculating air flow: Exchanger supply flow
VentSettings.S_AirFlowX(14) R Holding Register (4x) 0546 RW AV, 30546 100 Flow calculation X-constant for calculating air flow: Exchanger supply flow
VentSettings.S_AirFlowK(15)
R
Holding Register (4x)
0547
RW
AV, 30547
10
Flow calculation
K-constant for calculating air flow: Exchanger extract pressure
VentSettings.S_AirFlowX(15) R Holding Register (4x) 0548 RW AV, 30548 0 Flow calculation X-constant for calculating air flow: Exchanger extract pressure
VentSettings.S_DOSelect_SeqPumpY1(0) X Holding Register (4x) 0549 RW MSV, 30549 1 Operation override Running mode pump sequence-A
Modbus
0=Manual off
1=Manual on
2=Auto
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_DOSelect_SeqPumpY2 X Holding Register (4x) 0550 RW MSV, 30550 1 Operation override Running mode pump sequence-B
(See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY3 X Holding Register (4x) 0551 RW MSV, 30551 1 Operation override Running mode pump sequence-C
(See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY4 X Holding Register (4x) 0552 RW MSV, 30552 1 Operation override Running mode pump sequence-D
(See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY5 X Holding Register (4x) 0553 RW MSV, 30553 1 Operation override Running mode pump sequence-E
(See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY6 X Holding Register (4x) 0554 RW MSV, 30554 1 Operation override Running mode pump sequence-F
(See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY7 X Holding Register (4x) 0555 RW MSV, 30555 1 Operation override Running mode pump sequence-G
(See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY8 X Holding Register (4x) 0556 RW MSV, 30556 1 Operation override Running mode pump sequence-H
(See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY9 X Holding Register (4x) 0557 RW MSV, 30557 1 Operation override Running mode pump sequence-I
(See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY10 X Holding Register (4x) 0558 RW MSV, 30558 1 Operation override Running mode pump sequence-J
(See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_RecirculationAirDamper X Holding Register (4x) 0559 RW MSV, 30559 1 Operation override Running mode recirculation damper:
Modbus
0=Close
1=Open
2=Auto
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_DOSelect_OutdoorAirDamper X Holding Register (4x) 0560 RW MSV, 30560 1 Operation override Running mode outdoor air damper:
(See signal list for DOSelect_RecirculationAirDamper)
VentSettings.S_DOSelect_ExhaustAirDamper X Holding Register (4x) 0561 RW MSV, 30561 1 Operation override Running mode exhaust air damper:
(See signal list for DOSelect_RecirculationAirDamper)
VentSettings.S_DOSelect_HumidityStart X Holding Register (4x) 0562 RW MSV, 30562 1 Operation override Running mode humidity start signal
(See signal list for DOSelect_RecirculationAirDamper)
Page 27 of 45