Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentSettings.S_SAFManualOutput
R
Holding Register (4x)
0569
RW
AV, 30569
10
%
Operation override
Manual output supply air fan if running mode: Manual output
VentSettings.S_EAFAutoMode X Holding Register (4x) 0570 RW MSV, 30570 1 Operation override Running mode extract air fan:
(See signal list for SAFAutoMode)
VentSettings.S_EAFManualSetpoint
R
Holding Register (4x)
0571
RW
AV, 30571
10
P/Q
Operation override
Manual setpoint extract air fan if running mode: Manual setpoint
VentSettings.S_EAFManualOutput R Holding Register (4x) 0572 RW AV, 30572 10 % Operation override Manual output extract air fan if running mode: Manual output
VentSettings.S_ExternalControl X Holding Register (4x) 0573 RW MSV, 30573 1 Operation override External control:
Modbus
0=No External control,
1=Extended run speed 1,
2=Extended run speed 2,
3=Extended run speed 3,
4=External stop,
5=External stop with support control,
6=Start Free cooling,
7 = Recirculation
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_AirUnitServiceStop X Holding Register (4x) 0574 RW MSV, 30574 1 Operation override Stop the air handling unit with No 1 prio.
Modbus
0 = No
1 = Yes
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_SeqPumpOutdLimitYx(1)
R
Holding Register (4x)
0575
RW
AV, 30575
10
Unit setting
Outdoor temperature limit to allow pump stop sequence-A
VentSettings.S_SeqPumpOutdLimitYx(2) R Holding Register (4x) 0576 RW AV, 30576 10 Unit setting Outdoor temperature limit to allow pump stop sequence-B
VentSettings.S_SeqPumpOutdLimitYx(3)
R
Holding Register (4x)
0577
RW
AV, 30577
10
Unit setting
Outdoor temperature limit to allow pump stop sequence-C
VentSettings.S_SeqPumpOutdLimitYx(4)
R
Holding Register (4x)
0578
RW
AV, 30578
10
Unit setting
Outdoor temperature limit to allow pump stop sequence-D
VentSettings.S_SeqPumpOutdLimitYx(5) R Holding Register (4x) 0579 RW AV, 30579 10 Unit setting Outdoor temperature limit to allow pump stop sequence-E
VentSettings.S_SeqPumpOutdLimitYx(6)
R
Holding Register (4x)
0580
RW
AV, 30580
10
Unit setting
Outdoor temperature limit to allow pump stop sequence-F
VentSettings.S_SeqPumpOutdLimitYx(7) R Holding Register (4x) 0581 RW AV, 30581 10 Unit setting Outdoor temperature limit to allow pump stop sequence-G
VentSettings.S_SeqPumpOutdLimitYx(8) R Holding Register (4x) 0582 RW AV, 30582 10 Unit setting Outdoor temperature limit to allow pump stop sequence-H
VentSettings.S_SeqPumpOutdLimitYx(9)
R
Holding Register (4x)
0583
RW
AV, 30583
10
Unit setting
Outdoor temperature limit to allow pump stop sequence-I
VentSettings.S_SeqPumpOutdLimitYx(10) R Holding Register (4x) 0584 RW AV, 30584 10 Unit setting Outdoor temperature limit to allow pump stop sequence-J
VentSettings.S_VentControl X Holding Register (4x) 0585 RW MSV, 30585 1 Temperature setting Select temperature control type:
Modbus
0=Supply air
1=Supply air outdoor compensated
2=Room cascade
3=Extract air cascade
4=Room (summer) else supply air
5=Extract air (summer) else supply air
6=Room cascade outdoor compensated
7=Extract air cascade outdoor compensated
8=Extract air dependent supply air temperature
Bacnet
+1 offset for corresponding Modbus