Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentSettings.S_SAFLowspeedAirFlow(0)
R
Holding Register (4x)
0618
RW
AV, 30618
Q
Fan setting
Flow setpoint supply air fan low speed
4.3-1-00
VentSettings.S_SAFNormalspeedAirFlow
R
Holding Register (4x)
0619
RW
AV, 30619
Q
Fan setting
Flow setpoint supply air fan normal speed
4.3-1-00
VentSettings.S_SAFHighspeedAirFlow R Holding Register (4x) 0620 RW AV, 30620 1 Q Fan setting Flow setpoint supply air fan high speed 4.3-1-00
VentSettings.S_EAFLowspeedAirFlow(0)
R
Holding Register (4x)
0621
RW
AV, 30621
Q
Fan setting
Flow setpoint extract air fan low speed
4.3-1-00
VentSettings.S_EAFNormalspeedAirFlow R Holding Register (4x) 0622 RW AV, 30622 1 Q Fan setting Flow setpoint extract air fan normal speed 4.3-1-00
VentSettings.S_EAFHighspeedAirFlow R Holding Register (4x) 0623 RW AV, 30623 1 Q Fan setting Flow setpoint extract air fan high speed 4.3-1-00
VentSettings.S_SAFLowSpeedOutput(0)
R
Holding Register (4x)
0624
RW
AV, 30624
10
%
Fan setting
Output signal supply air fan low speed if manual control
VentSettings.S_SAFNormalSpeedOutput R Holding Register (4x) 0625 RW AV, 30625 10 % Fan setting Output signal supply air fan normal speed if manual control
VentSettings.S_SAFHighspeedOutput
R
Holding Register (4x)
0626
RW
AV, 30626
10
%
Fan setting
Output signal supply air fan high speed if manual control
VentSettings.S_EAFLowSpeedOutput(0)
R
Holding Register (4x)
0627
RW
AV, 30627
10
%
Fan setting
Output signal extract air fan low speed if manual control
VentSettings.S_EAFNormalSpeedOutput R Holding Register (4x) 0628 RW AV, 30628 10 % Fan setting Output signal extract air fan normal speed if manual control
VentSettings.S_EAFHighspeedOutput
R
Holding Register (4x)
0629
RW
AV, 30629
10
%
Fan setting
Output signal extract air fan high speed if manual control
VentSettings.S_SAFLowSpeedPressureOffset
R
Holding Register (4x)
0630
RW
AV, 30630
10
P
Fan setting
Offset supply air fan low speed if pressure control
VentSettings.S_SAFHighSpeedPressureOffset R Holding Register (4x) 0631 RW AV, 30631 10 P Fan setting Offset supply air fan high speed if pressure control
VentSettings.S_SAFLowSpeedAirFlowOffset
R
Holding Register (4x)
0632
RW
AV, 30632
Q
Fan setting
Offset supply air fan low speed if flow control
4.3-1-00
VentSettings.S_SAFHighSpeedAirFlowOffset
R
Holding Register (4x)
0633
RW
AV, 30633
Q
Fan setting
Offset supply air fan high speed if flow control
4.3-1-00
VentSettings.S_SAFLowSpeedOutputOffset R Holding Register (4x) 0634 RW AV, 30634 10 % Fan setting Offset supply air fan low speed if manual control
VentSettings.S_SAFHighSpeedOutputOffset
R
Holding Register (4x)
0635
RW
AV, 30635
10
%
Fan setting
Offset supply air fan high speed if manual control
VentSettings.S_EAFLowSpeedPressureOffset R Holding Register (4x) 0636 RW AV, 30636 10 P Fan setting Offset extract air fan low speed if pressure control
VentSettings.S_EAFHighSpeedPressureOffset R Holding Register (4x) 0637 RW AV, 30637 10 P Fan setting Offset extract air fan high speed if pressure control
VentSettings.S_EAFLowSpeedAirFlowOffset
R
Holding Register (4x)
0638
RW
AV, 30638
Q
Fan setting
Offset extract air fan low speed if flow control
4.3-1-00
VentSettings.S_EAFHighSpeedAirFlowOffset R Holding Register (4x) 0639 RW AV, 30639 1 Q Fan setting Offset extract air fan high speed if flow control 4.3-1-00
VentSettings.S_EAFLowSpeedOutputOffset
R
Holding Register (4x)
0640
RW
AV, 30640
10
%
Fan setting
Offset extract air fan low speed if manual control
VentSettings.S_EAFHighSpeedOutputOffset
R
Holding Register (4x)
0641
RW
AV, 30641
10
%
Fan setting
Offset extract air fan high speed if manual control
VentSettings.S_SAFModeFreeCool X Holding Register (4x) 0642 RW MSV, 30642 1 Operation override Selected speed in free cooling mode supply air fan:
Modbus
0=Off/Auto, normal setpoint
1=Manual setpoint
2=Manual output
3=Low speed setpoint
4=Normal speed setpoint
5=High speed setpoint
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_SAFManSetpFreeCool
R
Holding Register (4x)
0643
RW
AV, 30643
10
P/Q
Operation override
Manual setpoint in free cooling mode supply air fan
VentSettings.S_SAFManOutFreeCool R Holding Register (4x) 0644 RW AV, 30644 10 % Operation override Manual output in free cooling mode supply air fan
VentSettings.S_SAFModeFire X Holding Register (4x) 0645 RW MSV, 30645 1 Operation override Selected speed in fire mode supply air fan:
(See signal list for SAFModeFreeCool)
VentSettings.S_SAFManSetpFire R Holding Register (4x) 0646 RW AV, 30646 10 P/Q Operation override Manual setpoint in fire mode supply air fan
VentSettings.S_SAFManOutFire
R
Holding Register (4x)
0647
RW
AV, 30647
10
%
Operation override
Manual output in fire mode supply air fan
VentSettings.S_SAFModeSmoke X Holding Register (4x) 0648 RW MSV, 30648 1 Operation override Selected speed in smoke mode supply air fan:
(See signal list for SAFModeFreeCool)
VentSettings.S_SAFManSetpSmoke
R
Holding Register (4x)
0649
RW
AV, 30649
10
P/Q
Operation override
Manual setpoint in smoke mode supply air fan
VentSettings.S_SAFManOutSmoke R Holding Register (4x) 0650 RW AV, 30650 10 % Operation override Manual output in smoke mode supply air fan
VentSettings.S_SAFModeRecirculation X Holding Register (4x) 0651 RW MSV, 30651 1 Operation override Selected speed in recirculation mode supply air fan:
(See signal list for SAFModeFreeCool)
VentSettings.S_SAFManSetpRecirculation R Holding Register (4x) 0652 RW AV, 30652 10 P/Q Operation override Manual setpoint in recirculation mode supply air fan
VentSettings.S_SAFManOutRecirculation
R
Holding Register (4x)
0653
RW
AV, 30653
10
%
Operation override
Manual output in recirculation mode supply air fan
Page 31 of 45