Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentSettings.S_EAFModeFreeCool X Holding Register (4x) 0654 RW MSV, 30654 1 Operation override Selected speed in freecool mode extract air fan:
(See signal list for SAFModeFreeCool)
VentSettings.S_EAFManSetpFreeCool R Holding Register (4x) 0655 RW AV, 30655 10 P/Q Operation override Manual setpoint in freecool mode extract air fan
VentSettings.S_EAFManOutFreeCool
R
Holding Register (4x)
0656
RW
AV, 30656
10
%
Operation override
Manual output in freecool mode extract air fan
VentSettings.S_EAFModeFire X Holding Register (4x) 0657 RW MSV, 30657 1 Operation override Selected speed in fire mode extract air fan:
(See signal list for SAFModeFreeCool)
VentSettings.S_EAFManSetpFire
R
Holding Register (4x)
0658
RW
AV, 30658
10
P/Q
Operation override
Manual setpoint in fire mode extract air fan
VentSettings.S_EAFManOutFire R Holding Register (4x) 0659 RW AV, 30659 10 % Operation override Manual output in fire mode extract air fan
VentSettings.S_EAFModeSmoke X Holding Register (4x) 0660 RW MSV, 30660 1 Operation override Selected speed in smoke mode extract air fan:
(See signal list for SAFModeFreeCool)
VentSettings.S_EAFManSetpSmoke R Holding Register (4x) 0661 RW AV, 30661 10 P/Q Operation override Manual setpoint in smoke mode extract air fan
VentSettings.S_EAFManOutSmoke
R
Holding Register (4x)
0662
RW
AV, 30662
10
%
Operation override
Manual output in smoke mode extract air fan
VentSettings.S_EAFModeRecirculation X Holding Register (4x) 0663 RW MSV, 30663 1 Operation override Selected speed in recirculation mode extract air fan:
(See signal list for SAFModeFreeCool)
VentSettings.S_EAFManSetpRecirculation
R
Holding Register (4x)
0664
RW
AV, 30664
10
P/Q
Operation override
Manual setpoint in recirculation mode extract air fan
VentSettings.S_EAFManOutRecirculation
R
Holding Register (4x)
0665
RW
AV, 30665
10
%
Operation override
Manual output in recirculation mode extract air fan
VentSettings.S_EAFFrequencyFact R Holding Register (4x) 0666 RW AV, 30666 10 Fan setting Flow slave factor extract air fan if fan control type: Supply air pressure
with extract air flow slave
VentSettings.S_ExtractPID_Pband R Holding Register (4x) 0667 RW AV, 30667 10 PID setting P-band extract air temperature
VentSettings.S_ExtractPID_Itime R Holding Register (4x) 0668 RW AV, 30668 1 PID setting I-time extract air temperature
VentSettings.S_SAFPID_Pband
R
Holding Register (4x)
0669
RW
AV, 30669
10
PID setting
P-band pressure supply air fan
VentSettings.S_SAFPID_Itime R Holding Register (4x) 0670 RW AV, 30670 1 PID setting I-time pressure supply air fan
VentSettings.S_EAFPID_Pband
R
Holding Register (4x)
0671
RW
AV, 30671
10
PID setting
P-band pressure extract air fan
VentSettings.S_EAFPID_Itime
R
Holding Register (4x)
0672
RW
AV, 30672
PID setting
I-time pressure extract air fan
VentSettings.S_FrostPID1_PBand(0) R Holding Register (4x) 0673 RW AV, 30673 10 PID setting P-band freeze protection 1
VentSettings.S_FrostPID1_ITime(0)
R
Holding Register (4x)
0674
RW
AV, 30674
PID setting
I-time freeze protection 1
VentSettings.S_FrostPID2_Pband
R
Holding Register (4x)
0675
RW
AV, 30675
10
PID setting
P-band freeze protection 2
VentSettings.S_FrostPID2_ITime R Holding Register (4x) 0676 RW AV, 30676 1 PID setting I-time freeze protection 2
VentSettings.S_FrostPID3_Pband
R
Holding Register (4x)
0677
RW
AV, 30677
10
PID setting
P-band freeze protection 3
VentSettings.S_FrostPID3_ITime R Holding Register (4x) 0678 RW AV, 30678 1 PID setting I-time freeze protection 3
VentSettings.S_CO2PID_Pband R Holding Register (4x) 0679 RW AV, 30679 10 PID setting P-band CO₂
VentSettings.S_CO2PID_Itime
R
Holding Register (4x)
0680
RW
AV, 30680
PID setting
I-time CO₂
VentSettings.S_RoomPID_Pband R Holding Register (4x) 0681 RW AV, 30681 10 PID setting P-band room temperature
VentSettings.S_RoomPID_Itime
R
Holding Register (4x)
0682
RW
AV, 30682
PID setting
I-time room temperature
VentSettings.S_DeIcePID_Pband
R
Holding Register (4x)
0683
RW
AV, 30683
10
PID setting
P-band defrosting
VentSettings.S_DeIcePID_Itime R Holding Register (4x) 0684 RW AV, 30684 1 PID setting I-time defrosting
VentSettings.S_HumidityPID_Pband
R
Holding Register (4x)
0685
RW
AV, 30685
10
PID setting
P-band humidity control
VentSettings.S_HumidityPID_Itime
R
Holding Register (4x)
0686
RW
AV, 30686
PID setting
I-time humidity control
VentSettings.S_ExtraPID_Pband R Holding Register (4x) 0687 RW AV, 30687 10 PID setting P-band extra controller
VentSettings.S_ExtraPID_Itime
R
Holding Register (4x)
0688
RW
AV, 30688
PID setting
I-time extra controller
VentSettings.S_SAFAirFlowPID_Pband
R
Holding Register (4x)
0689
RW
AV, 30689
PID setting
P-band flow supply air fan
4.3-1-00
VentSettings.S_SAFPID_Itime R Holding Register (4x) 0690 RW AV, 30690 1 PID setting I-time flow supply air fan
VentSettings.S_EAFAirFlowPID_Pband
R
Holding Register (4x)
0691
RW
AV, 30691
PID setting
P-band flow extract air fan
4.3-1-00
VentSettings.S_EAFPID_Itime R Holding Register (4x) 0692 RW AV, 30692 1 PID setting I-time flow extract air fan
VentSettings.S_SeqY1PID_Pband R Holding Register (4x) 0693 RW AV, 30693 10 PID setting P-band sequence-A
VentSettings.S_SeqY1PID_ITime
R
Holding Register (4x)
0694
RW
AV, 30694
PID setting
I-time sequence-A
VentSettings.S_SeqY2PID_Pband R Holding Register (4x) 0695 RW AV, 30695 10 PID setting P-band sequence-B
VentSettings.S_SeqY2PID_ITime
R
Holding Register (4x)
0696
RW
AV, 30696
PID setting
I-time sequence-B
VentSettings.S_SeqY3PID_Pband
R
Holding Register (4x)
0697
RW
AV, 30697
10
PID setting
P-band sequence-C
Page 32 of 45