Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentSettings.S_FrostProtSPStop(1)
R
Holding Register (4x)
0770
RW
AV, 30770
10
Unit setting
Setpoint freeze protection 2 if standby mode
VentSettings.S_FrostProtPGain(1) R Holding Register (4x) 0771 RW AV, 30771 10 Unit setting P-band freeze protection 2 if running mode
(setpoint=alarm limit+P-band)
VentSettings.S_FrostProtSPRun(2)
R
Holding Register (4x)
0772
RW
AV, 30772
10
Alarm setting
Alarm limit freeze protection alarm 3
VentSettings.S_FrostProtSPStop(2) R Holding Register (4x) 0773 RW AV, 30773 10 Unit setting Setpoint freeze protection 3 if standby mode
VentSettings.S_FrostProtPGain(2) R Holding Register (4x) 0774 RW AV, 30774 10 Unit setting P-band freeze protection 3 if running mode
(setpoint=alarm limit+P-band)
VentSettings.S_ExtraControllerSetP R Holding Register (4x) 0775 RW AV, 30775 10 T Extra controller Setpoint extra controller
VentSettings.S_ExtraControllerMode X Holding Register (4x) 0776 RW MSV, 30776 1 Extra controller Control mode extra controller
Modbus
0=Heating Controller
1=Cooling Controller
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_SumAlarm1(0) X Holding Register (4x) 0777 RW MSV, 30777 1 Unit setting Setting for sum alarm 1 (alarm levels)
Modbus
0=Off
1=A+B+C
2=A+B
3=B+C
4=A+C
5=A
6=B
7=C
Bacnet
+1 offset for corresponding Modbus
VentSettings.S_SumAlarm2 X Holding Register (4x) 0778 RW MSV, 30778 1 Unit setting Setting for sum alarm 2 (alarm levels)
(See signal list for SumAlarm1(0))
VentSettings.S_AlarmOutput X Holding Register (4x) 0779 RW AV, 30779 1 Unit setting Setting of alarm number used for universal alarm output
Status:
0=Off
1=AlaPt(1)=Ala_MalfunctionSAF1
2=AlaPt(2)=Ala_MalfunctionSAF2
etc.
VentSettings.S_SupplyMaxDiff
R
Holding Register (4x)
0780
RW
AV, 30780
10
T
Alarm setting
Alarm limit deviation alarm supply air temperature
VentSettings.S_SupplyHighAlarmLimit R Holding Register (4x) 0781 RW AV, 30781 10 T Alarm setting Alarm limit high supply air temperature
VentSettings.S_SupplyLowAlarmLimit
R
Holding Register (4x)
0782
RW
AV, 30782
10
T
Alarm setting
Alarm limit low supply air temperature
VentSettings.S_EfficiencyLowLimit
R
Holding Register (4x)
0783
RW
AV, 30783
10
%
Alarm setting
Alarm limit low efficiency exchanger
VentSettings.S_RoomHighLimit R Holding Register (4x) 0784 RW AV, 30784 10 T Alarm setting Alarm limit high room temperature
VentSettings.S_RoomLowLimit
R
Holding Register (4x)
0785
RW
AV, 30785
10
T
Alarm setting
Alarm limit low room temperature
VentSettings.S_ExtractAirTempHigh
R
Holding Register (4x)
0786
RW
AV, 30786
10
T
Alarm setting
Alarm limit high extract air temperature
VentSettings.S_ExtractAirTempLow R Holding Register (4x) 0787 RW AV, 30787 10 T Alarm setting Alarm limit low extract air temperature
VentSettings.S_SAFMaxDiffPressure
R
Holding Register (4x)
0788
RW
AV, 30788
10
P
Alarm setting
Alarm limit deviation alarm supply air fan
VentSettings.S_EAFMaxDiffPressure R Holding Register (4x) 0789 RW AV, 30789 10 P Alarm setting Alarm limit deviation alarm extract air fan
VentSettings.S_RecircSetP R Holding Register (4x) 0790 RW AV, 30790 10 Recirculation Setpoint recirculation if temperature control
Page 35 of 45