Operation and Maintenance Instructions

Table Of Contents
Maintenance
|
25
7.13 How to replace the fan module
When ordering a replacement fan module, note if it is supply or extract fan. This is important for the fan to get the cor-
rect Modbus address.
For size Topvex SC35 the door beam has to be removed, figure 10.
1. Disconnect the fast coupling to the electric wire
2. Disconnect the blue and red tubes from the supply air fan (standard units with CAV). Blue tube is connected to the
cone (1) of the fan, the red tube is connected to measuring nipple on the wall or on the sheet metal on the suction
side.
3. Loosen the bolts on the rails on each side of the fan to remove the fan.
4. Put the new fan in place and connect the electric wire and tubes.
5. Fasten the fan with the rails and bolts.
214959 | A007