QUICK CONFIGURATION GUIDE ACCESS SW 4 0 1 04 TO 4 6 1 00 157618A008

Table Of Contents
Quick configuration guides |
9
5.4.2 Configuration
Configure the number of connected room temperature sensors in the Configuration > Functions > Tempera-
ture control menu.
Overview:
Configuration > Functions > Temperature control
24 Jun 10:31
Room temperature sensor
2
Calculation mode room temperature
Average
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Temperature control
4. Select number of connected Room temperature sensors
5. Select Calculation mode room temperature (more than one room temperature sensor)
5.4.3 Allocation
Select I/O (in-/output) placement for where the room temperature sensors are connected to the controller in the Con-
figuration > I/O allocation settings > Analog inputs menu.
Overview:
Configuration > I/O allocation settings > Analog
inputs
24 Jun 10:31
Analog inputs
Device Position
Room temperature 1
Controller Select I/O
Room temperature 2
Controller Select I/O
Room temperature 3
Controller Select I/O
Room temperature 4
Controller Select I/O
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Analog inputs
4. Select the input connected to the sensor (e.g. UI1) as position for Room temperature 1/2/3/4
5. Repeat step 4 for any remaining room temperature sensors.
157618 | A008