QUICK CONFIGURATION GUIDE ACCESS SW 4 0 1 04 TO 4 6 1 00 157618A008

Table Of Contents
22
| Quick configuration guides
5.10.2 Configuration
Configure what type of cooler is connected in the Configuration > Functions > Function activation > Heat-
ing/Cooling sequence setup > Cooling menu.
Overview:
Configuration >. .. > Heating/Cooling sequence setup >
Cooling
24 Jun 10:31
Type of sequence Cooling
Type of cooler
DX
Type of feedback
Alarm
Digital start output
Yes
Run indication from DX-compressor
Yes
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Heating/Cooling sequence setup
4. Select Cooling (SEQ-C)
5. Set Type of sequence to Cooling
6. Select the type of cooler (e.g. DX)
7. Select the type of feedback from the cooler as Type of feedback (e.g. Alarm or Run indication)
8. Select Yes as Digital start output if the external cooler requires a digital start signal.
9. Select Yes as Run indication from DX-compressor if available on external cooler.
5.10.3 Allocation
Select I/O (in-output) placement of where the cooler control signal output, digital start output and feedback input are
connected to the controller in the Configuration > I/O allocation settings submenus Digital inputs,
Analog outputs and Digital outputs.
Overview:
Configuration > I/O allocation settings > Digital
inputs
24 Jun 10:31
Digital inputs
Device Position
Feedback cooling (SEQ-C)
Controller UI4
Run indication DX-compressor (SEQ-C)
Controller Select I/O
Configuration > I/O allocation settings > Analog
outputs
24 Jun 10:31
Analog outputs
Device Position
Cooling (SEQ-C)
Controller AO4
157618 | A008