Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentActual.A_AlaPt(94)
L
Input Status Register (1x)
0104
R
Alarm point
High outdoor air temperature
VentActual.A_AlaPt(95)
L
Input Status Register (1x)
0105
R
Alarm point
Low outdoor air temperature
VentActual.A_AlaPt(96) L Input Status Register (1x) 0106 R Alarm point Freeze protection alarm 1
VentActual.A_AlaPt(97)
L
Input Status Register (1x)
0107
R
Alarm point
Freeze protection alarm 2
VentActual.A_AlaPt(98) L Input Status Register (1x) 0108 R Alarm point Freeze protection alarm 3
VentActual.A_AlaPt(99) L Input Status Register (1x) 0109 R Alarm point High limit extra sensor 1
VentActual.A_AlaPt(100)
L
Input Status Register (1x)
0110
R
Alarm point
Low limit extra sensor 1
VentActual.A_AlaPt(101) L Input Status Register (1x) 0111 R Alarm point High limit extra sensor 2
VentActual.A_AlaPt(102)
L
Input Status Register (1x)
0112
R
Alarm point
Low limit extra sensor 2
VentActual.A_AlaPt(103)
L
Input Status Register (1x)
0113
R
Alarm point
High limit extra sensor 3
VentActual.A_AlaPt(104) L Input Status Register (1x) 0114 R Alarm point Low limit extra sensor 3
VentActual.A_AlaPt(105)
L
Input Status Register (1x)
0115
R
Alarm point
High limit extra sensor 4
VentActual.A_AlaPt(106)
L
Input Status Register (1x)
0116
R
Alarm point
Low limit extra sensor 4
VentActual.A_AlaPt(107) L Input Status Register (1x) 0117 R Alarm point High limit extra sensor 5
VentActual.A_AlaPt(108)
L
Input Status Register (1x)
0118
R
Alarm point
Low limit extra sensor 5
VentActual.A_AlaPt(109)
L
Input Status Register (1x)
0119
R
BV, 20119
Alarm point
High limit selected sensor 1
VentActual.A_AlaPt(110) L Input Status Register (1x) 0120 R BV, 20120 Alarm point Low limit selected sensor 1
VentActual.A_AlaPt(111)
L
Input Status Register (1x)
0121
R
BV, 20121
Alarm point
High limit selected sensor 2
VentActual.A_AlaPt(112) L Input Status Register (1x) 0122 R BV, 20122 Alarm point Low limit selected sensor 2
VentActual.A_AlaPt(113) L Input Status Register (1x) 0123 R BV, 20123 Alarm point Manual operation air handling unit
VentActual.A_AlaPt(114)
L
Input Status Register (1x)
0124
R
BV, 20124
Alarm point
Manual operation supply air
VentActual.A_AlaPt(115) L Input Status Register (1x) 0125 R BV, 20125 Alarm point Manual operation supply air fan
VentActual.A_AlaPt(116)
L
Input Status Register (1x)
0126
R
BV, 20126
Alarm point
Manual operation extract air fan
VentActual.A_AlaPt(117)
L
Input Status Register (1x)
0127
R
BV, 20127
Alarm point
Manual operation heater
VentActual.A_AlaPt(118) L Input Status Register (1x) 0128 R BV, 20128 Alarm point Manual operation exchanger
VentActual.A_AlaPt(119)
L
Input Status Register (1x)
0129
R
BV, 20129
Alarm point
Manual operation cooler
VentActual.A_AlaPt(120)
L
Input Status Register (1x)
0130
R
BV, 20130
Alarm point
Manual operation damper
VentActual.A_AlaPt(121) L Input Status Register (1x) 0131 R BV, 20131 Alarm point Manual operation pump heater
VentActual.A_AlaPt(122)
L
Input Status Register (1x)
0132
R
BV, 20132
Alarm point
Manual operation pump exchanger
VentActual.A_AlaPt(123) L Input Status Register (1x) 0133 R BV, 20133 Alarm point Manual operation pump cooler
VentActual.A_AlaPt(124) L Input Status Register (1x) 0134 R BV, 20134 Alarm point Manual operation damper recirculation
VentActual.A_AlaPt(125)
L
Input Status Register (1x)
0135
R
BV, 20135
Alarm point
Manual operation damper outdoor air
VentActual.A_AlaPt(126) L Input Status Register (1x) 0136 R BV, 20136 Alarm point Manual operation damper exhaust air
VentActual.A_AlaPt(127)
L
Input Status Register (1x)
0137
R
BV, 20137
Alarm point
Manual operation fire damper
VentActual.A_AlaPt(128)
L
Input Status Register (1x)
0138
R
BV, 20138
Alarm point
Manual control sequence-A
VentActual.A_AlaPt(129) L Input Status Register (1x) 0139 R BV, 20139 Alarm point Manual control sequence-B
VentActual.A_AlaPt(130)
L
Input Status Register (1x)
0140
R
BV, 20140
Alarm point
Manual control sequence-C
VentActual.A_AlaPt(131)
L
Input Status Register (1x)
0141
R
BV, 20141
Alarm point
Manual control sequence-D
VentActual.A_AlaPt(132) L Input Status Register (1x) 0142 R BV, 20142 Alarm point Manual control sequence-E
VentActual.A_AlaPt(133)
L
Input Status Register (1x)
0143
R
BV, 20143
Alarm point
Manual control sequence-F
VentActual.A_AlaPt(134)
L
Input Status Register (1x)
0144
R
BV, 20144
Alarm point
Manual control sequence-G
VentActual.A_AlaPt(135) L Input Status Register (1x) 0145 R BV, 20145 Alarm point Manual control sequence-H
VentActual.A_AlaPt(136)
L
Input Status Register (1x)
0146
R
BV, 20146
Alarm point
Manual control sequence-I
VentActual.A_AlaPt(137) L Input Status Register (1x) 0147 R BV, 20147 Alarm point Manual control sequence-J
VentActual.A_AlaPt(138) L Input Status Register (1x) 0148 R BV, 20148 Alarm point Output in manual operation
VentActual.A_AlaPt(139)
L
Input Status Register (1x)
0149
R
BV, 20149
Alarm point
Input in manual operation
VentActual.A_AlaPt(140) L Input Status Register (1x) 0150 R BV, 20150 Alarm point Manual operation extra controller
VentActual.A_AlaPt(141)
L
Input Status Register (1x)
0151
R
BV, 20151
Alarm point
Manual operation external fan motor 1
VentActual.A_AlaPt(142)
L
Input Status Register (1x)
0152
R
BV, 20152
Alarm point
Manual operation external fan motor 2
Page 41 of 45