Operation and Maintenance Instructions

Table Of Contents
Troubleshooting |
31
8 Troubleshooting
Check or correct the following before contacting your service representative. Always check if there are any alarms ac-
tive in the control panel (chapter 9).
1. Fan(s) do not start
Check if there are any alarm messages.
Check the settings in the control panel (times, week schedule, auto/manual operation etc.).
Check if the fuses has tripped.
2. Reduced airflow
Check if there are any alarm messages.
Check the settings for normal and low fan speed.
Check if any reduced speed input is active.
Check if filters need changing.
Check that the outdoor/exhaust air damper (if used) opens.
Check if diffusers and louvres need cleaning.
Check diffuser/louvre openings.
Check if fans and exchanger block need cleaning.
Check if the roof unit or air intake is clogged.
Check ducts for visible damage and/or build up of dust/pollution.
3. Cold supply air
Check if there are any alarm messages.
Check if the fans have stopped. If so the alarm relay might have tripped (shown as fan alarm in the control panel).
Check the temperature settings in the control panel.
Check if the extract filter must be changed.
Check if the overheating thermostat has tripped. After the heater has cooled down, press the red button on the
electrical heater.
4. Noise/vibrations
Check that the unit is completely levelled.
Clean the fan impellers.
Check that the screws holding the fans are tightened properly.
214959 | A007