QUICK CONFIGURATION GUIDE ACCESS SW 4 0 1 04 TO 4 6 1 00 157618A008

Table Of Contents
Quick configuration guides |
19
5.8.4 Operation settings
Set up the Fire damper test settings in the Data & Settings > Fire/Smoke menu.
Note:
Only applicable if fire damper test is configured.
Overview:
Data & Settings > Fire/Smoke
24 Jun 10:31
Run time fire damper 90 s
Test interval fire damper 7 days
Test hour fire damper 15
Step by step:
1.
Select Data & Settings from the navigation icons
2. Select Fire/Smoke
3. Set max allowed fire damper run time as Run time fire damper
4. Set day interval between fire damper tests as Test interval fire damper
5. Select hour (1-24) for start of fire damper test as Test hour fire damper, e.g 15 means the fire damper test will
initiate at 3 pm (15:00) on test day.
5.9 Free cooling
5.9.1 Activation
Select Yes as Free Cooling from the list of available functions in the Configuration > Functions > Function
activation menu.
Overview:
Configuration > Functions > Function activation
24 Jun 10:31
Free cooling
Yes
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Yes as Free cooling
157618 | A008