QUICK CONFIGURATION GUIDE ACCESS SW 4 0 1 04 TO 4 6 1 00 157618A008

Table Of Contents
Quick configuration guides |
27
5.11.3 Allocation
Select I/O (in-output) placement of where the heater control signal output, pump start output and pump feedback input
are connected to the controller in the Configuration > I/O allocation settings submenus Digital inputs,
Analog outputs and Digital outputs.
Overview:
Configuration > I/O allocation settings > Digital
inputs
24 Jun 10:31
Digital inputs
Device Position
Feedback heating (SEQ-A)
Controller UI4
Configuration > I/O allocation settings > Analog
outputs
24 Jun 10:31
Analog outputs
Device Position
Heating (SEQ-A)
Controller AO4
Configuration > ... > Analog outputs > Heating (SEQ-A)
24 Jun 10:31
Range output
0-10 V
Configuration > I/O allocation settings > Digital
outputs
24 Jun 10:31
Digital outputs
Device Position
Heating pump (SEQ-A)
Controller DO1
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Digital inputs
4. Select the input connected to the circulation pump’s feedback contact (e.g. UI4) as position for Feedback heating
(SEQ-A)
5. Go back to I/O allocation settings (use the navigation path Configuration > I/O allocation
settings)
6. Select Analog outputs
7. Select the analog output connected to the valve actuator control signal (e.g. AO4) as position for Heating (SEQ-A)
8. Select Heating (SEQ-A)
9. Adjust Range output to fit with the signal range of the valve actuator (e.g. 0-10 V)
10.Go back to I/O allocation settings (use the navigation path Configuration > I/O allocation
settings)
11.Select Digital outputs
12.Select the digital output connected to the circulation pump (e.g. DO1) as postion for Heating pump (SEQ-A).
157618 | A008