Configuration Manual

Version Document
A
001
A
ccess V4.X Configuration manual
43 (56) 2018-07-11
related to any control functions. “Extra Sensor 1” should be used for external
setpoint input.
Extra alarm
No
Yes
If selection are yes, 1..10 extra alarm can be configured under I/O allocation
I/O allocation settings
Configure: Configuration
22.1 Analog inputs
Configure: Configuration > I/O allocation
Analog inputs shows only sensors/signals that are activated by configuration
Note! If the sensor/signal is not in the list, please activate and configure the function and
go back in this list to set up a physical position of I/O’s
Analouge inputs Device Signal
e.g Supply air temperature Controller AI1
Avalible analogues inputs
Outdoor temperature
Intake air temperature
Supply air temperature
Exhaust air temperature
Extract air temperature
Room temperature 1
Room temperature 2
Room temperature 3
Room temperature 4
Pressure supply air
Pressure extract air
Flow supply air
Flow extract air
Flow exchanger supply air
Pressure exchanger extract air
Defrosting temperature
Frost protection temperature 1
Frost protection temperature 2
Frost protection temperature 3
CO2 room/extract air
Humidity sensor room/extract air
Humidity sensor supply air
Humidity outdoor
Extra controller temperature
External control supply air fan
External control extract air fan
Extra sensor 1
Extra sensor 2
Extra sensor 3
Extra sensor 4
Extra sensor 5
External setpoint temperature
External setpoint flow
Pressure filter supply air
Pressure filter extract air
Efficiency temperature exchanger
Device
Select controller or some off the other device.
Note! If you not find your device, se 25.2 to configure/activate your device
Signal
Select I/O for signal on selected device.
Note! It’s possible to select an already used I/O position.
Please select the same ouputs as wiring diagram describe.
Or select a free I/O’s position.
22.2 Digital inputs
Configure: Configuration > I/O allocation
Digital inputs shows only sensors/signals that are activated by configuration