Configuration Manual

Version Document ID
A
001 Access 4x Configuration manual
50 (56) 2018-07-11
Function
Configure: Configuration > System Settings > Device List > Device (n) > Functin >
….
Model Fan
(Modbus)
Rotary
exchanger
(Modbus) *1
Pressure
transmitter
Damper
(Modbus)
Expansion unit
(EXOline)
Function Supply air fan Heating *1 Exp1 Heating *1 Exp1
Exhaust air fan Exchanger*1 Exp2 Exchanger*1 Exp2
Cooling *1 Exp3 Coolingc *1 Exp3
Recirculation 1 *1 Exp4 Recirculation 1 *1 Exp4
Recirculation 2 *1 Exp5 Recirculation 2 *1 Exp5
Fan heating/cooling
*1
Exp6 Fan heating/cooling
*1
Exp6
Heating 2 *1 Exp7 Heating 2 *1 Exp7
Cooling 2 *1 Exp8 Cooling 2 *1 Exp8
Exchanger extract *1 Exp9 Exchanger extract *1 Exp9
Extra heating/cooling
capacity *1
Exp10 Extra heating/cooling
capacity *1
Exp10
Recirculation air
Outdoor air
Exhaust air
*1 Only active sequence are selecteble
Name
Configure: Configuration > System Settings > Device List > Device (n) > Name
Device (n)
Select a unique device name.
This name will be used in Device “drop down list” when you select Device
under I/O allocation.
25.3 Preference unit settings
Configure: Configuration > System Settings
Temperature unit
Celsius
Fahrenheit
Flow unit
m³/h
CFM
m³/s
l/s
Pressure unit
Pa
In.wg(x100)