Installation Instruction
Table Of Contents
- 1 Product information
- 2 Overview
- 3 Warnings
- 4 Unloading from trailer
- 5 Transport and storage
- 6 Unpacking
- 7 Duct connections
- 8 Internal components
- 9 Installation
- 10 Electrical connections
- 11 Connection of water heating coil
- 12 Access control system
- 13 Connect accessories in Control unit CU27-C
- 14 Dimensions and weight
- 15 Technical data
- 16 Additional equipment
- 17 Disposal
- 18 EU Declaration of Conformity
- 19 UK Declaration of Conformity
Installation |
11
Location for installation
• Place the outdoor air duct in the northern or eastern side of the building, away from other exhaust outlets.
• Make sure inspection doors are accessible for maintenance.
• Free space for opening of doors and taking out components for service (see dimension drawing).
• Avoid placing the unit against a wall. If not possible, insulate carefully.
Electrical
• Do not cut the mains power supply to the unit if installed in an colder area.
• Do not expose the electronic components lower temperature than 0° C and higher than +50° C.
• An all pole circuit breaker with a minimum 3 mm gap must precede the unit's electrical connection to the mains
power supply.
• Connect the unit electrically to the mains power supply through a safety switch (available as an accessory). Connect
the wiring to the electrical cabinet. See the air handling unit’s wiring diagram.
Before operation
• Remove and install enclosed parts.
• Connect ducts or provide with protection.
• Remove package material from the unit.
• Close the doors.
214958 | A007