Commissioning Record

18
| Alarm configuration
71
Extra alarm 4 B No action 5s
72
Extra alarm 5 B No action 5s
73
Extra alarm 6 B No action 5s
74
Extra alarm 7 B No action 5s
75
Extra alarm 8 B No action 5s
76
Extra alarm 9 B No action 5s
77
Extra alarm 10 B No action 5s
78
Internal battery error
B No action 5s
79
Alarm service interval C No action 1s
80
Restart blocked after power on
C
Fast stop
0s
81
Deviation alarm supply air temperature
- No action 4m 5°C
82
Deviation alarm supply air fan
- No action 4m 500
83
Deviation alarm extract air fan - No action 4m 500
84
Deviation alarm humidity control
- No action 30m 10%
85
Deviation alarm extra controller - No action 30m 10°C
86
High supply air temperature
A
Normal stop
300s 35°C
87
Low supply air temperature
A
Normal stop
300s 10°C
90
High room temperature
-
No action 30m 30°C
162527 | A004