Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentActual.A_AlaPt(193)
L
Input Status Register (1x)
0202
R
BV, 20202
Alarm point
Malfunction extract air fan 6
4.3-1-00
VentActual.A_AlaPt(194)
L
Input Status Register (1x)
0203
R
BV, 20203
Alarm point
Malfunction extract air fan 7
4.3-1-00
VentActual.A_AlaPt(195) L Input Status Register (1x) 0204 R BV, 20204 Alarm point Malfunction extract air fan 8 4.3-1-00
VentActual.A_AlaPt(196)
L
Input Status Register (1x)
0205
R
BV, 20205
Alarm point
Alarm supply air fan 6
4.3-1-00
VentActual.A_AlaPt(197) L Input Status Register (1x) 0206 R BV, 20206 Alarm point Alarm supply air fan 7 4.3-1-00
VentActual.A_AlaPt(198) L Input Status Register (1x) 0207 R BV, 20207 Alarm point Alarm supply air fan 8 4.3-1-00
VentActual.A_AlaPt(199)
L
Input Status Register (1x)
0208
R
BV, 20208
Alarm point
Alarm extract air fan 6
4.3-1-00
VentActual.A_AlaPt(190) L Input Status Register (1x) 0209 R BV, 20209 Alarm point Alarm extract air fan 7 4.3-1-00
VentActual.A_AlaPt(200)
L
Input Status Register (1x)
0210
R
BV, 20210
Alarm point
Alarm extract air fan 8
4.3-1-00
VentActual.A_AlaPt(201)
L
Input Status Register (1x)
0211
R
BV, 20211
Alarm point
Warning supply air fan 6
4.3-1-00
VentActual.A_AlaPt(202) L Input Status Register (1x) 0212 R BV, 20212 Alarm point Warning supply air fan 7 4.3-1-00
VentActual.A_AlaPt(203)
L
Input Status Register (1x)
0213
R
BV, 20213
Alarm point
Warning supply air fan 8
4.3-1-00
VentActual.A_AlaPt(204)
L
Input Status Register (1x)
0214
R
BV, 20214
Alarm point
Warning extract air fan 6
4.3-1-00
VentActual.A_AlaPt(205) L Input Status Register (1x) 0215 R BV, 20215 Alarm point Warning extract air fan 7 4.3-1-00
VentActual.A_AlaPt(206)
L
Input Status Register (1x)
0216
R
BV, 20216
Alarm point
Warning extract air fan 8
4.3-1-00
VentActual.A_AlaPt(207)
L
Input Status Register (1x)
0217
R
BV, 20217
Alarm point
Malfunction heating zone 1
4.3-1-00
VentActual.A_AlaPt(208) L Input Status Register (1x) 0218 R BV, 20218 Alarm point Malfunction heating zone 2 4.3-1-00
VentActual.A_AlaPt(209)
L
Input Status Register (1x)
0219
R
BV, 20219
Alarm point
Malfunction heating zone 3
4.3-1-00
VentActual.A_AlaPt(210) L Input Status Register (1x) 0220 R BV, 20220 Alarm point Malfunction cooling zone 1 4.3-1-00
VentActual.A_AlaPt(211) L Input Status Register (1x) 0221 R BV, 20221 Alarm point Malfunction cooling zone 2 4.3-1-00
VentActual.A_AlaPt(212)
L
Input Status Register (1x)
0222
R
BV, 20222
Alarm point
Malfunction cooling zone 3
4.3-1-00
VentActual.A_AlaPt(213) L Input Status Register (1x) 0223 R BV, 20223 Alarm point Deviation alarm supply temperature zone 1 4.3-1-00
VentActual.A_AlaPt(214)
L
Input Status Register (1x)
0224
R
BV, 20224
Alarm point
Deviation alarm supply temperature zone 2
4.3-1-00
VentActual.A_AlaPt(215)
L
Input Status Register (1x)
0225
R
BV, 20225
Alarm point
Deviation alarm supply temperature zone 3
4.3-1-00
VentActual.A_AlaPt(216) L Input Status Register (1x) 0226 R BV, 20226 Alarm point Freeze protection alarm zone 1 4.3-1-00
VentActual.A_AlaPt(217)
L
Input Status Register (1x)
0227
R
BV, 20227
Alarm point
Freeze protection alarm zone 2
4.3-1-00
VentActual.A_AlaPt(218)
L
Input Status Register (1x)
0228
R
BV, 20228
Alarm point
Freeze protection alarm zone 3
4.3-1-00
VentActual.A_AlaPt(219) L Input Status Register (1x) 0229 R BV, 20229 Alarm point Electric heater is overheated zone 1 4.3-1-00
VentActual.A_AlaPt(220)
L
Input Status Register (1x)
0230
R
BV, 20230
Alarm point
Electric heater is overheated zone 2
4.3-1-00
VentActual.A_AlaPt(221) L Input Status Register (1x) 0231 R BV, 20231 Alarm point Electric heater is overheated zone 3 4.3-1-00
VentActual.A_AlaPt(222) L Input Status Register (1x) 0232 R Alarm point Sensor error supply air temp zone 1 4.3-1-00
VentActual.A_AlaPt(223)
L
Input Status Register (1x)
0233
R
Alarm point
Sensor error supply air temp zone 2
4.3-1-00
VentActual.A_AlaPt(224) L Input Status Register (1x) 0234 R Alarm point Sensor error supply air temp zone 3 4.3-1-00
VentActual.A_AlaPt(225)
L
Input Status Register (1x)
0235
R
Alarm point
Sensor error room temp zone 1
4.3-1-00
VentActual.A_AlaPt(226)
L
Input Status Register (1x)
0236
R
Alarm point
Sensor error room temp zone 2
4.3-1-00
VentActual.A_AlaPt(227) L Input Status Register (1x) 0237 R Alarm point Sensor error room temp zone 3 4.3-1-00
VentActual.A_AlaPt(228)
L
Input Status Register (1x)
0238
R
Alarm point
Sensor error extract temp zone 1
4.3-1-00
VentActual.A_AlaPt(229)
L
Input Status Register (1x)
0239
R
Alarm point
Sensor error extract temp zone 2
4.3-1-00
VentActual.A_AlaPt(230) L Input Status Register (1x) 0240 R Alarm point Sensor error extract temp zone 3 4.3-1-00
VentActual.A_AlaPt(231)
L
Input Status Register (1x)
0241
R
Alarm point
Sensor error freeze protection zone 1
4.3-1-00
VentActual.A_AlaPt(232)
L
Input Status Register (1x)
0242
R
Alarm point
Sensor error freeze protection zone 2
4.3-1-00
VentActual.A_AlaPt(233) L Input Status Register (1x) 0243 R Alarm point Sensor error freeze protection zone 3 4.3-1-00
VentActual.A_AlaPt(234)
L
Input Status Register (1x)
0244
R
Alarm point
Signal error feedback cooling valve
4.5-1-00
VentActual.A_AlaPt(235) L Input Status Register (1x) 0245 R Alarm point Signal error feedback outdoor air damper 4.5-1-00
VentActual.A_AlaPt(236) L Input Status Register (1x) 0246 R Alarm point Signal error feedback recirculation damper 4.5-1-00
VentActual.A_AlaPt(237)
L
Input Status Register (1x)
0247
R
BV, 20247
Alarm point
Device warning
4.6-1-00
VentActual.A_AlaPt(238) L Input Status Register (1x) 0248 R BV, 20248 Alarm point Device alarm 4.6-1-00
VentActual.A_AlaPt(239)
L
Input Status Register (1x)
0249
R
BV, 20249
Alarm point
High pressure EATR
4.6-1-00
VentActual.A_AlaPt(240)
L
Input Status Register (1x)
0250
R
Alarm point
Sensor error pressure EATR
4.5-1-00