E0 R MO GB SE
INSTRUCTION
i
Read this instruction before installation
and wiring of the product
Display/button-function repeater
Corrigo E0-R and E0-R230K are display/button-function repeaters.
They can be used when there is need for a remote display and the
distance between controller and display/buttons is more than
10 meters preventing direct connection of the display unit. E-DSP or
ED9100 can be used as display units.
Using the RS485 port it can address up to 6 connected Corrigo units.
The repeater can also be used in a network with EXOcompact.
Technical data
Max total length communication line 1200 m
Wiring
Communication line
G
G0
1
2
3
Corrigo E0-R / E0-R230K
B
A
N
E
50
51
52
53
*24 V AC (E0-R)
230 V AC (E0-R230K)
Ext. disp.
E-DSP alt. ED9100
Power supply*
Wiring of the RS485 communication line
Use shielded twisted pair cable. Connect A to A and B to B. Connect the
shield to N.
Communication line
B
A
N
E
50
51
52
53
B
A
N
E
B
A
N
E
Corrigo controller
Corrigo controller
Corrigo E0-R / E0-R230K
50
51
52
53
50
51
52
53
Conguration
On power-up, E0-R... will display the Base Display.
Corrigo E DSP
07:04:17 14:38
Select Controller
with down arrow
To set the date and time, click on the OK button to log in.
Click the down button to access the controller selection list where you
choose which of the connected controllers you wish to communicate with,
the Settings menu where you set the addresses to the connected control-
lers and the Access rights menu where you can administer passwords.
Controller 1
Controller 2
Controller 3
Controller 4
Controller 5
Controller 6
Settings
Access rights
Settings
Click down-button until you reach the menu Settings.
Click right-button.
Controller 1
PLA: 254
ELA: 30
Here you can change the text that is displayed in the controller selec-
tion list and set the addresses for the connected controllers.
The text in the top line can be changed to any suitable text to identify
the controller. Use up-button and down-button to scroll through the
available characters. Use right-button and left-button to move side-
ways in the text. To store the revised text, click OK. The revised text
will be displayed in the controller selection list.
The connected controllers are identied by their ELA and PLA add-
resses. Each connected unit must be set to a unique address. See
the Corrigo manual for information on how to change the controller
address.
If less than 6 units are connected leave the unused controller addres-
ses at PLA: 0 and ELA: 0. You can however still change the text if you
wish, for example to Not used.
For instance, if you have three controllers that you wish to monitor,
called Riverside Building Heating 1, Riverside Building Heating 2 and
Riverside Building Ventilation, the menu list could look like this:
Riverside Bd Heat 1
Riverside Bd Heat 2
Riverside Bd Vent
Not used
Not used
Not used
Settings
Access rights
E0-R / E0-R230K
6764B
DEC 07
EN
1