INSTALLATION OPERATION AND MAINTENANCE INSTRUCTION ZRS CE002

4 Push the fan and steering rods into the chimney. It is not
necessary to attach the fan with screws in the chimney,
the steering rods keeps the fan in position.
5 Attach the supplied steel wire. The steel wire keeps the
product on the roof when it is temporarily lifted away from
the chimney during chimney sweeping. The product is
not supplied with screws and plug to attach the steel wire.
6 Connect the mains supply to the connection box of the
product. Refer to 12.3 Wiring diagrams page 12.
Note:
The cable has a steel housing that can discolour over time
as it weathers in. The coloring of the steel housing will not
decrease the protection of the cable.
5 Electrical connection
5.1 To do before the electrical
connection
Make sure that the electrical connection agrees with the
product specification on the motor name plate.
Make sure that the environment for electrical connection
is clean and dry.
Make sure that the wiring diagram that is included with the
supply of the product agrees with the terminals in the con-
nection box.
5.2 To connect the product to the
power supply
Complete the electrical connection for the motor. Refer to
the motor wiring diagram that is included with the product.
Make sure that the cross section of the protective earthing
is equal to or larger than the cross section of the phase
conductor.
Install a circuit breaker in the permanent electrical installa-
tion, with a contact opening of a minimum 3 mm at each
pole.
If a residual current device (RCD) is installed, make sure
that it is an all-current sensitive RCD. Consider if the prod-
uct has a frequency converter, uninterruptible power sup-
ply (UPS), or an EC motor. EC motors have a leakage
current to earth that is <=3.5 mA.
5.3 Speed controller for AC
motors
Note:
The speed controller alternatives are different for different
motor types. Make sure that your motor is compatible with
the speed controller type before you use it.
The speed can be controlled by voltage reduction using a
transformer. It is also possible to control the fan speed with
frequency converter if the installed frequency converter has
built in all-pole sine filter and shielded cables are not needed.
5.4 To install motor protection for
AC motors
If the product has an built in motor protection, reset by dis-
connecting the product from power for 60 seconds.
If the motor has temperature monitors such as thermal
contacts (TK) or thermistors lead out into the terminal box,
these must always be connected in the control circuit us-
ing appropriate motor protection.
Make sure that an overheated motor cannot start again
automatically when it becomes cool.
Install the motor cables and the temperature monitor apart.
If the motor does not have temperature monitors, install a
motor protection switch.
5