Original instructions SIRe Basic Fan Heaters Water With quick guide SIReB C SE .... 2 GB .... 13 DE .... 24 FR .... 35 ES .... 46 IT NL .... 68 NO .... 79 PL .... 89 RU .... 100 .... 57 For wiring diagram, please see last pages.
GB SIRe Basic Fan Heaters Water Quick guide/start up Check that all constituent parts are present (see section Constituent parts). Advice about location Control unit SIReUB1 has an integrated room temperature sensor and is installed so that it is easily accessible to the user. RJ12 (6p/6c) modular cables, which are available in different lengths, are used to connect the PC board and the control unit. Longer cables are available as options. Maximum cable lengths see section Options.
GB SIRe Basic Fan Heaters Water Start up System supplied with power. Three digits 1.4.0. (software version) is quickly shown in the status window followed by three horizontal lines. After about 30 seconds the prevailing room temperature is then shown in the status window. Use arrow up/down and set the desired room temperature, fan speed step and heating step. To change a setting push the round button (confirm), the setting will start to flash and can be adjusted by using the arrow up/down.
SIRe Basic Fan Heaters Water GB Contents Quick guide/start up Advice about location Connect the system Wiring diagrams Enter ID/Operation without control unit Start up 13 13 13 13 14 Constituent parts SIReB 16 Option 17 Max.
GB SIRe Basic Fan Heaters Water Constituent parts SIReB Integrated in fan heater C PE N L SUPPLY 230V X5 C2 SIReUB1, control unit Basic Wall unit cover X4 C1 X3 ROOM ACTUATOR 230V SIReB1/B2, integrated PC Board Base SIReIT, internal temperature sensor SIReCC, modular cable Dimensions constituent parts Typ Description SIReUB1 SIReB1 SIReIT SIReCC605 Controll unit Integrated PC board Base Intern temperature sensor Modular cable RJ12 (6/6) 16 HxWxD [mm] 120x70x35 L [m] 1 5
GB SIRe Basic Fan Heaters Water Option SIReRTX, external room temperature sensor SIReCJ4, joint piece SIReCC, modular cable SIReCJ6, joint piece Type Description HxWxD SIReRTX SIReCJ4 SIReCJ6 SIReCC603 SIReCC605 SIReCC610 SIReCC615 SIReCC403 SIReCC405 SIReCC410 External room temperature sensor Joint piece for two pcs. RJ11 (4/4) Joint piece for two pcs.
GB SIRe Basic Fan Heaters Water Water control - valve kit VOS SD230 TBVC Water control - option BPV10 AV SD230 VOSP TBVCMP BPV10 AV VAT, adjustment tool for valve package. VOT SD230 TRVS Type RSK-no.
SIRe Basic Fan Heaters Water GB Operating modes Set values Operating modes Use arrow up /down to choose desired room temperature, fan speed step and heating step. In factory settings the fan runs in auto mode. Auto mode Set maximum fan speed and the thermostat controls the heat by open/close actuator/ valve and successive increase/decrease fan speed. When the desired room temperature is reached the actuator/valv will close and the fan stops. Maximum fan speed in Auto mode is limited to step 4.
GB SIRe Basic Fan Heaters Water Control unit SIReUB1 Overview Prevailing room temperature 2 0. 8 C Statuswindow Arrow up Scroll up Confirm Arrow down Scroll down C Desired room temperature 20 Fan speed step Alarm Red led Run signal Green led ON/OFF button - 3 Heating step _ 1 Explanations Status window The status window has four main displays: prevailing and desired room temperature, fan and heating steps. Alarm codes and parameter settings can also be shown in the status window.
GB SIRe Basic Fan Heaters Water Installer menu Parameter menu Keep Confirm button pressed until P00 is shown in the status window. Use arrow up / down to scroll between the parameters. Press Confirm button once to change a setting in the parameter menu. Flashing values can be adjusted using the arrow up/down and then confirm. Keep the Confirm button pressed to return to the status window. (Returning automatically to the status window after about 50 seconds). P.
GB SIRe Basic Fan Heaters Water Alarm and error codes Overheat protection Only applies to units with internal sensor. The over heating protection is intended to restrict the exhaust temperature to +90 °C. At +90 °C the actuator for heat supply will close. Actuator will open again if the internal temperature drops below +85 °C. If the temperature continues to rise despite this, for example because of a faulty valve/ actuator, the fan will start to spin at +95 °C to keep the temperature down.
SIRe Basic Fan Heaters Water GB Table - Alarm Alarm Cause A.FA Motor alarm Thermal switch has deployed. One or several motors have overheated. (Only units with withdrawn thermal switches.) A.ot Over heating alarm Action Check that nothing is obstructing the unit’s air intake and exhaust. When the overheated motor has cooled the thermal switch shuts again and the alarm can be reset. At repeated alarms, check the motors, replace damaged motors.
Pot.
SIRe Basic Fan Heaters Water Wiring diagram Basic parallell SIReB1 SIReSD230 C2 Pot. X5 Unit ID C1 X4 ROOM X3 230V~ ACTUATOR SUPPLY N L PE PE N L SIReB1 C2 Pot. X5 Unit ID SIReSD230 C1 X4 ROOM X3 230V~ ACTUATOR SUPPLY N L PE PE N L SIReB1 C2 Pot.
Tel: +46 31 336 86 00 Fax: +46 31 26 28 25 mailbox@frico.se www.frico.se For latest updated information and information about your local contact: www.frico.