Original instructions SIRe Basic Fan Heaters Electric With quick guide SIReBX C For wiring diagram, please see last pages.
GB SIRe Basic Fan Heaters Electric Quick guide/start up Enter ID/Operation without control unit Check that all constituent parts are present (see section Constituent parts). The control system can control one or more units in parallel (max 9). Each unit must get a unique ID number (1-9) which is set in the ID selector of the PC board. E.g. Unit 1: ID=1, unit 2: ID=3 If the external control for some reason has not been installed the unit can still be run temporarily.
GB SIRe Basic Fan Heaters Electric Start up System supplied with power. Three digits 1.4.0. (software version) is quickly shown in th the status window followed by three horizontal lines. After about 30 seconds the prevailing room temperature is then shown in the status window. After the first start up the following basic settings are made. Use arrow up/down and set the desired room temperature, fan speed step and heating step.
SIRe Basic Fan Heaters Electric GB Contents Quick guide/start up Advice about location Connect the system Wiring diagrams Enter ID/Operation without control unit Start up 11 11 11 11 12 Constituent parts SIReBX 14 Option 15 Max.
GB SIRe Basic Fan Heaters Electric Constituent parts SIReBX C SIReUB1, control unit Basic Wall unit cover SIReB1X, External PC board Basic SIReIT02, internal temperature sensor 2m SIReCC, modular cables Dimensions constituent parts Type Description SIReUB1 SIRB1X SIReIT02 SIReCC605 Control unit PC Board Base Internal sensor Modular cable RJ12 (6/6) 14 HxWxD [mm] 120x70x35 L [m] 2 5
GB SIRe Basic Fan Heaters Electric Option SIReRTX, external room temperature sensor SIReCJ4, joint piece SIReCJ6, joint piece SIReCC, modular cable Type RSK-no. E-no.
GB SIRe Basic Fan Heaters Electric Operating modes Set values Operating modes Use arrow up /down to choose desired room temperature, fan speed step and heating step. Factory settings gives manual control of fan and heating controlled by thermostat at choosen step. SE06-15 SE20 SE30 Fansteps Heatsteps 4 2 2 2 2 3 Push the confirm button and the digit(s) starts to flash. The value can now be adjusted using the arrow up /down, and confirm.
GB SIRe Basic Fan Heaters Electric Control unit SIReUB1 Overview Prevailing room temperature C Statuswindow Arrow up Scroll up 2 0. 8 Confirm Arrow down Scroll down C Desired room temperature 20 Alarm Red led Run signal Green led ON/OFF button Fan speed step Heating step _ 3 2 Explanations Confirm Status window To have access to the Installers menu, choose parameters and cofirm an adjusted setting.
GB SIRe Basic Fan Heaters Electric Installer menu Parameter menu Keep Confirm button pressed until P00 is shown in the status window. Use arrow up / down to scroll between the parameters. Press Confirm button once to change a setting in the parameter menu. Flashing values can be adjusted using the arrow up/down and then confirm. Keep the Confirm button pressed to return to the status window. (Returning automatically to the status window after about 50 seconds). P.P0. 0.01 PPP..0.00222 P 0P.21 3 P.
GB SIRe Basic Fan Heaters Electric Alarm and error codes Overheat protection SE06-15: The over heating protection is intended to restrict the exhaust temperature to 70 °C. At 70 °C an output step is tripped off. If the temperature continues to rise all output is interrupted at 75 °C. If the temperature continues to rise despite this, for example because of a faulty contactor, the fan will start to spin at 70 °C to keep the temperature down.
GB SIRe Basic Fan Heaters Electric Table - Alarm Alarm Cause Action Thermal switch has deployed. One or several motors have overheated. (Only units with withdrawn thermal switches.) Check that nothing is obstructing the unit’s air intake and exhaust. When the overheated motor has cooled the thermal switch shuts again and the alarm can be reset. At repeated alarms, check the motors, replace damaged motors.
SIRe Basic Fan Heaters Electric Connections between SIReB1X and Panther SE06, SE09, SE12 and SE15.
SIRe Basic Fan Heaters Electric Connections between SIReB1X and Panther SE20 L L~ N SIReB1X SE20 41
SIRe Basic Fan Heaters Electric Connections between SIReB1X and Panther SE30 L L~ N SIReB1X SE30 42
C2 Pot.
SIRe Basic Fan Heaters Electric Wiring diagram Basic parallel SIReB1X Pot. Unit ID Pot. Unit ID ≠ SIReRTX SIReB1 C2 Pot. X5 Unit ID C1 X4 ROOM X3 ACTUATOR SUPPLY N L~ L PE N SIReUB1 L C SIReB1 C2 Pot.