Original instructions Pamir 3500/4200/5000 EN .... 21 SE .... 26 NO .... 32 FR .... 38 DE ....44 NL .... 50 ES ....56 IT ....62 PL .... 68 RU .... 74 FI .... 81 DK ....
Pamir 3500/4200/5000 EN The introduction pages consist mainly of pictures. For translation of the English texts used, see the respective language pages. SE Introduktionssidorna består huvudsakligen av bilder. För översättning av de engelska texter som används, se respektive språksidor. NO Introduksjonssidene består hovedsakelig av bilder. For oversettelse av de engelske tekstene, se de respektive språksidene FR Les pages de présentation contiennent principalement des images.
Pamir 3500/4200/5000 Pamir 3500 DN20 (3/4"), outside thread 270 36 Horizontal mounting L 525 127 2 m; 2,5 m 205 PAFEC3510 PAFEC3515 PAFEC3520 PAFEC3525 43 364 92 A 40 L [mm] 1039 1549 2039 2549 A [mm] 40 40 40 39 1, 1,5 m: 4 x M8 2 m: 6 x M8 2,5 m: 8 x M8 FC Vertical mounting 36 525 PAFEC3515 PAFEC3520 PAFEC3525 L1 [mm] 1572 2062 2572 L2 [mm] 1515 2004 2515 40 23 L1 L2 270 3
Pamir 3500/4200/5000 Pamir 4200/5000 Horizontal mounting 295 36 DN20 (3/4"), outside thread L 127 2 m; 2,5 m 235 43 404 102 A 611 FC 40 PAFEC4210/5010 PAFEC4215/5015 PAFEC4220/5020 PAFEC4225/5025 L [mm] 1039 1549 2039 2549 A [mm] 40 40 40 39 PAFEC4215/5015 PAFEC4220/5020 PAFEC4225/5025 L1 [mm] 1572 2062 2572 L2 [mm] 1515 2004 2515 1, 1,5 m: 4 M8 2 m: 6 M8 2,5 m: 8 M8 Vertical mounting 40 23 4 611 36 L2 L1 295
Pamir 3500/4200/5000 2 Service hatch 1 Fig. 1A: Open the unit. Loosen Remove Fig. 1B: To remove the front plate, the locking devices on both sides must be loosened. When the front is reinstalled, it is important to ensure that it is firmly seated in the front locks. Terminal block Gland min 100 Gland PC board FC Fig. 2: PC board FC is integrated within the air curtain at delivery. Fig. 3: Minimum distance.
Pamir 3500/4200/5000 Water connection 2 Fig. 4a: NOTE! Use a pipe wrench or a similar tool to grip the air curtain connections to prevent straining of the pipes. A B C D B A Fig.
Pamir 3500/4200/5000 M8-holes for mountings PAFEC 3510 / 3515 / 4210 / 4215 / 5010 / 5015 L PAFEC3510 PAFEC4210 PAFEC5010 PAFEC3515 PAFEC4215 PAFEC5015 L [mm] 750 750 750 1260 1260 1260 PAFEC3500 PAFEC4200 875 PAFEC5000 A [mm] 205 235 235 127 L 127 L A B A B A B 127 127 875 B [mm] 92 102 102 127 875 875 127 875 875 A B A B A B PAFEC3520 / 4220 / 5020 745 770 745 127 745 770 745 745 770 745 A B 127 B PAFEC3525 / 4225 / 5025 A B A 127 Fig.
Pamir 3500/4200/5000 Accessories - horizontal mounting PA34WB / PAWBL A D D C A B 19 11 [mm] PA34WB PAWBL A B C D E F G 80 40 40 120 40 400 408 120 60 52,5 165 60 560 568 E E F B C 20 mm Fig. 6: See separate manual for PA34WB/PAWBL.
Pamir 3500/4200/5000 Accessories - horizontal mounting PA34CB PA34TR (PA34VD) Fig. 7: PA34TR + PA34CB + PA34VD. See separate manual for PA34TR. Item number 18059 18060 18061 18062 18063 18064 18056 18057 18058 18065 18066 18067 PA34WS (PA34CB) Fig.8: PA34WS + PA34CB See separate manual for PA34WS.
Pamir 3500/4200/5000 Accessories - horizontal mounting Item number 19085 19086 19087 19088 19090 19091 19092 19093 Type Item number 110834 110835 110836 110837 110838 110839 110840 110841 Type PA3XT10 PA3XT15 PA3XT20 PA3XT25 PA4XT10 PA4XT15 PA4XT20 PA4XT25 PA3DW10 PA3DW15 PA3DW20 PA3DW25 PA4DW10 PA4DW15 PA4DW20 PA4DW25 Length PAFEC 3510 PAFEC 3515 PAFEC 3520 PAFEC 3525 PAFEC 4210 / 5010 PAFEC 4215 / 5015 PAFEC 4220 / 5020 PAFEC 4225 / 5025 130-200 mm 130-200 mm 130-200 mm 130-200 mm 130-200 mm 130-2
Pamir 3500/4200/5000 Accessories - vertical mounting Note! The air curtain must be secured in the wall or ceiling. 32 PA3VDW PA4VDW 32 PA3JK PA4JK Fig. 11: See separate manual for PA3JK / PA4JK.
Pamir 3500/4200/5000 Accessories 2 PA34EF Item number 19064 19065 19066 19067 17597 18055 88906 FHDN DTV200S Type PA34EF10 PA34EF15 PA34EF20 PA34EF25 DTV200S* FHDN20 FHDN2010 Length PAFEC 3510W / 4210W / 5010W PAFEC 3515W / 4215W / 5015W PAFEC 3520W / 4220W / 5020W PAFEC 3525W / 4225W / 5025W PAFEC 3500W / 4200W / 5000W PAFEC 3500W / 4200W / 5000W PAFEC 3500W / 4200W / 5000W 350 mm 1000 mm *) See separate manual.
Pamir 3500/4200/5000 Control systems The air curtain must be supplemented with a control system.
Pamir 3500/4200/5000 PAFEC3500 A PAFEC4200 A PAFEC5000 A 4210/5010: 3 Motors 4215/5015: 4 Motors 4220/5020: 6 Motors 4225/5025: 7 Motors M M GND GND Sensor I1 I2 O1O2 N Heating N L PE PE 230V IN Trafo N H1 H2 Motor L FCBASE REA Motor B1 B2 D1 D2 Termination A1 A2 BUS 2 HI LO ON LO GND +12V OFF BUS 1 GND +12V HI M GND 0-10V PWM Alarm 3510: 2 Motors 3515: 3 Motors 3520: 4 Motors 3525: 5 Motors PAFEC/ARFEC 3500 A PAFEC/ARFEC 4200 A PAFEC/ARFEC 5000 A 230V~ Wiring diagrams for co
Pamir 3500/4200/5000 PAFEC3510/15 E PAFEC4210/15 E PAFEC5010/15 E 3510: 2 Motors 3515: 3 Motors 4210/5010: 3 Motors 4215/5015: 4 Motors M M M TS1 TS2 K2 K1 Inlet sensor Outlet sensor GND GND Sensor I1 I2 O1O2 FCBASEPCB REA L1 L2 L3 N Heating N L PE PE 230V IN Trafo N H1 H2 Motor N GND 0-10V PWM Alarm L Motor B1 B2 D1 D2 Termination A1 A2 BUS 2 HI LO ON LO GND +12V OFF BUS 1 GND +12V HI PAFEC/ARF PAFEC/ARF PAFEC/ARF 230V~ 400V 3~ Wiring diagrams for control system in the
LO HI LO GND +12V M GND GND Trafo FCBASEPCB REA Outlet sensor Inlet sensor M I1 I2 O1O2 4220/5020: 6 Motors 4225/5025: 7 Motors Sensor Motor GND +12V HI L PE PE 230V IN N Wiring diagrams for control system in the FC manual.
Pamir 3500/4200/5000 PAFEC3500 W PAFEC4200 W PAFEC5000 W 3510: 3515: 3520: 3525: 2 3 4 5 4210/5010: 3 Motors 4215/5015: 4 Motors 4220/5020: 6 Motors 4225/5025: 7 Motors Motors Motors Motors Motors M M M Inlet sensor Outlet sensor GND Motor I1 I2 O1O2 N Motor L GND 0-10V PWM Alarm E1 E2 - + Actuator WTA 24V BaseW Sensor GND B1 B2 D1 D2 Termination A1 A2 BUS 2 HI LO ON LO GND +12V OFF BUS 1 GND +12V HI N L PE PE 230V IN Trafo PAFEC/ARFEC 3500 W PAFEC/ARFEC 4200 W PAFEC/ARFEC 5
Pamir 3500/4200/5000 Technical specifications Pamir 3500 Voltage motor: 230V~ 1 Ambient, no heat - PAFEC3500 A (IP24**) Item number Type Output Airflow*1 189577 189581 189585 189589 PAFEC3510A PAFEC3515A PAFEC3520A PAFEC3525A [kW] 0 0 0 0 [m3/h] 900/1800 1400/2700 1900/3500 2350/4400 3 Electrical heat - PAFEC3500 E (IP20) Item Type number 189576 189580 189584 189588 PAFEC3510E08 PAFEC3515E12 PAFEC3520E16 PAFEC3525E20 Output steps [kW] 2,7/5,4/8,1 3,9/7,8/12 5,4/11/16 6,6/13/20 Airflow*1 ∆t*4
Pamir 3500/4200/5000 Technical specifications Pamir 4200 Voltage motor: 230V~ 1 Ambient, no heat - PAFEC4200 A (IP24**) Item number Type Output Airflow*1 230355 230360 230365 230370 PAFEC4210A PAFEC4215A PAFEC4220A PAFEC4225A [kW] 0 0 0 0 [m3/h] 1200/2400 1800/3500 2300/4700 3100/6150 3 Electrical heat - PAFEC4200 E (IP20) Item Type number 230356 230361 230366 230371 PAFEC4210E12 PAFEC4215E18 PAFEC4220E24 PAFEC4225E30 Output steps [kW] 3,9/7,8/12 6,0/12/18 7,8/16/24 9,9/20/30 Airflow*1 ∆t*4
Pamir 3500/4200/5000 Technical specifications Pamir 5000 Voltage motor: 230V~ 1 Ambient, no heat - PAFEC5000 A (IP24**) Item number Type Output Airflow*1 230375 230379 230383 230387 PAFEC5010A PAFEC5015A PAFEC5020A PAFEC5025A [kW] 0 0 0 0 [m3/h] 900/2950 1350/4200 1700/5900 2150/7200 3 Electrical heat - PAFEC5000 E (IP20) Item Type number 230376 230380 230384 230388 PAFEC5010E12 PAFEC5015E18 PAFEC5020E24 PAFEC5025E30 Output steps [kW] 3,9/7,8/12 6,0/12/18 7,8/16/24 9,9/20/30 Airflow*1 ∆t*4 [
Pamir 3500/4200/5000 EN Installation and operating instructions General Instructions Mounting Application Horizontal mounting Read these instructions carefully prior to installation and use. Keep this manual for future reference. The product may only be used as set out in the assembly and operating instructions. The guarantee is only valid should the product be used in the manner intended and in accordance with the instructions.
EN Pamir 3500/4200/5000 Vertical mounting Units from 1,5 metres and longer may be used vertically. The air curtain is mounted vertically as close as possible to the door. For the best effect air curtains should be placed on both sides of the opening. For vertical mounting, each unit must be supplemented with a vertical kit PA3JK/PA4JK. The unit can be reversed and placed on either side of the door.
Pamir 3500/4200/5000 Connecting the water coil (W) The installation must be carried out by an authorized installer. The water coil has copper tubes with aluminium fins and is suitable for connection to a closed water heating system. Steel connection pipe. The heating coil must not be connected to a mains pressure water system or an open water system. Note that the unit shall be preceded by a regulating valve, see Frico valve kit.
EN Pamir 3500/4200/5000 All units Since fan motors and other components are maintenance-free, no maintenance other than cleaning is necessary. The level of cleaning can vary depending on local conditions. Undertake cleaning at least twice a year. Inlet and exhaust grilles, impeller and elements can be vacuum cleaned or wiped using a damp cloth. Use a brush when vacuuming to prevent damaging sensitive parts. Avoid the use of strong alkaline or acidic cleaning agents.
Pamir 3500/4200/5000 Residual current circuit breaker (E) When the installation is protected by means of a residual current circuit breaker, which trips when the appliance is connected, this may be due to moisture in the heating element. When an appliance containing a heater element has not been used for a long period or stored in a damp environment, moisture can enter the element.