VSC OPERATION AND MAINTENANCE INSTRUCTIONS 4 118 0324 2 IOM

13
Topvex FC
Compact Air Handling Unit
Operation and Maintenance Instructions
Document in original language
125918-EN_GB
2015-03-16 A001
Operation and Maintenance Instructions
Systemair AB
Main menu item Sub-menu item 1 Sub-menu item 2 Explanations
Frequency
control manual SAF
Output: %
Frequency control manual
SAF
Output 1/1: 75%
Output 1/2: 50%
Outdoor comp.output.
–20°C = 0 m³/h
0°C = 0 m³/h
Act. Comp: 0
/h
Frequency
control manual EAF
Output: %
Frequency control manual
EAF
Output 1/1: 75%
Output 1/2: 50%
Outdoor comp.output.
–20°C = 0 m³/h
0°C = 0 m³/h
Act. Comp: 0
/h
Flow control SAF
Actual: m³/h
Setp.: m³/h
Airow for the supply air fan
(constant airow control).
Only visible if the unit is
congured for “Flow control”
(CAV).
Flow control SAF
Setp 1/1: 1100 m³/h
Setp 1/2: 550 m³/h
Set the normal (1/1) and
reduced (1/2) airow for the
supply air fan.