VSC OPERATION AND MAINTENANCE INSTRUCTIONS 4 118 0324 2 IOM
14
Topvex FC
Compact Air Handling Unit
Operation and Maintenance Instructions
Document in original language
125918-EN_GB
2015-03-16 A001
Operation and Maintenance Instructions
Systemair AB
Main menu item Sub-menu item 1 Sub-menu item 2 Explanations
Outdoor
comp.Setp.
–20°C = 0 m³/h
0°C = 0 m³/h
Act. Comp: 0
m³/h
Set the SAF airow compensation for the
settable outdoor temperature.
The outdoor compensation is linear
and is set using two parameter
pairs which give the value of the
compensation at two dierent
outdoor temperatures. The
compensation can be positive
or negative.
Shows the actual airow
compensation.
Flow control
EAF
Actual: xxx
m³/h
Setp.:xxx m³/h
Airow for the extract air fan (constant
airow control).
Only visible if the unit is congured for
“Flow control” (CAV).
Flow control EAF
Setp 1/1: 1100
m³/h
Setp 1/2: 550
m³/h↓
Set the normal (1/1) and reduced (1/2)
airow for the extract air fan.
Outdoor
comp.Setp.
–20°C = 0 m³/h
0°C = 0 m³/h
Act. Comp: 0
m³/h
Set the EAF airow compensation for the
settable outdoor temperature.
The outdoor compensation is linear and is
set using two parameter pairs which give
the value of the compensation at two die-
rent outdoor temperatures.
The compensation can be positive or
negative.
Shows the actual airow compensation.
Pressure
control SAF
Actual: Pa
Setp.: Pa
The actual external pressure and set point
for the supply air fan.
Only visible if the unit is congured for
„Pressure control“ (VAV)
Pressure control
SAF
Setp 1/1: 200
Pa
Setp 1/2: 100
Pa
Set the external pressure set
point for normal speed (1/1)
and reduced speed (1/2) for the
supply air fan.