VSC OPERATION AND MAINTENANCE INSTRUCTIONS 4 118 0324 2 IOM

20
Topvex FC
Compact Air Handling Unit
Operation and Maintenance Instructions
Document in original language
125918-EN_GB
2015-03-16 A001
Operation and Maintenance Instructions
Systemair AB
Main menu item Sub-menu item 1 Sub-menu item 2 Explanations
Flow control SAF
P-band: 10000.0
/h
I-me: 10.0
sec
Min. output:
0%
Set P-band, I-time and Min. output for the
supply air fan when the unit comes congu-
red as Flow control from factory. Alternative-
ly Pressure control if that conguration is
chosen
Flow control EAF
P-band: 10000.0
/h
I-me: 10.0
sec
Min. output:
0%
Set P-band, I-time and Min. output for the
supply air fan when the unit comes congu-
red as Flow control from factory. Alternative-
ly Pressure control if that conguration is
chosen
→ Alarm
sengs
→ Alarm limits
Set the alarm limits and allowed deviations
for the di󰀨erent functions
→ Alarm delays
Set the alarm delays and allowed deviation
delays for the di󰀨erent functions
→ Restore alarm
Reset the service alarm (lter alarm).
Restore factory
sengs: No
Restore user
sengs: No
In this menu, it is possible to restore all
parameters to their factory settings or to
the user settings they were saved as
earlier.
Select Yes or No
Save user
sengs
No
The current conguration can be saved in
a separate memory area and can later be
restored using the previous menu,
Restore user settings.
Select Yes or No
Darker gray area, log in
to “Administrator level”
code 3333
→ Conguraon
Inputs/Outputs
Setup for inputs and outputs.
Sensor sengs
Setup of sensor types and boundaries for
the regulation range.