VSC OPERATION AND MAINTENANCE INSTRUCTIONS 4 118 0324 2 IOM
20
Topvex FC
Compact Air Handling Unit
Operation and Maintenance Instructions
Document in original language
125918-EN_GB
2015-03-16 A001
Operation and Maintenance Instructions
Systemair AB
Main menu item Sub-menu item 1 Sub-menu item 2 Explanations
Flow control SAF
P-band: 10000.0
m³/h
I-me: 10.0
sec
Min. output:
0%
Set P-band, I-time and Min. output for the
supply air fan when the unit comes congu-
red as Flow control from factory. Alternative-
ly Pressure control if that conguration is
chosen
Flow control EAF
P-band: 10000.0
m³/h
I-me: 10.0
sec
Min. output:
0%
Set P-band, I-time and Min. output for the
supply air fan when the unit comes congu-
red as Flow control from factory. Alternative-
ly Pressure control if that conguration is
chosen
→ Alarm
sengs
→ Alarm limits
Set the alarm limits and allowed deviations
for the dierent functions
→ Alarm delays
Set the alarm delays and allowed deviation
delays for the dierent functions
→ Restore alarm
Reset the service alarm (lter alarm).
Restore factory
sengs: No
Restore user
sengs: No
In this menu, it is possible to restore all
parameters to their factory settings or to
the user settings they were saved as
earlier.
Select Yes or No
Save user
sengs
No
The current conguration can be saved in
a separate memory area and can later be
restored using the previous menu,
Restore user settings.
Select Yes or No
Darker gray area, log in
to “Administrator level”
code 3333
→ Conguraon
→
Inputs/Outputs
Setup for inputs and outputs.
→
Sensor sengs
Setup of sensor types and boundaries for
the regulation range.