VSC OPERATION AND MAINTENANCE INSTRUCTIONS 4 118 0324 2 IOM

29
Topvex FC
Compact Air Handling Unit
Operation and Maintenance Instructions
Document in original language
125918-EN_GB
2015-03-16 A001
Operation and Maintenance Instructions
Systemair AB
5.3.2 Changing Supply/Extract air lter
The lter cannot be cleaned and must be changed when necessary. New lters can be ordered from
Systemair. Operation time between lter changes depends on the air pollution at the installation site. A
di󰀨erential pressure switch indicates when it’s time to change the lters. This will trigger an alarm in
the control panel.
When this occurs do the following:
1. Replace the lters with new ones as described below.
2. Acknowledge the alarm by pressing the red button on the control panel (pos.1 gure 3) followed by OK
(pos.4 gure 3).
3. Choose →Acknowledge by pressing OK.
Open the door as described in chapter 5.3.1.
Fig. 5 Changing the lters