Modbus for residential D24810 User manual(A007)

7.15Registerfordemandcontrol
NameRegister
address
RorR/W
NVMAccess
(Reg./Coil)
Description/remarks
REG_DEMC_CO2_SP
851
R/W
RegRange:0-2000
0:Off
REG_DEMC_CO2_P_BAND
852
R/W
RegRange:1-2000
REG_DEMC_CO2_I_TIME
853
R/W
RegRange:1-120
0:nointegration
REG_DEMC_RH_SP_SUMMER
854
R/W
RegRange:0-100
0:Off
Note:oldregistername(before
PCU-EC4programversion5.09.00)is
REG_DEMC_RH_SP
REG_DEMC_RH_P_BAND
855
R/W
RegRange:1-100
REG_DEMC_RH_I_TIME
856
R/W
RegRange:1-120
0:nointegration
REG_DEMC_STATE
857RReg
0:Startup
1:Waitingforsensornetwork
2:Waitingforsensordata
3:Automode
4:normalmode
REG_DEMC_MODBUS_CO2_VALUE
858WRegValueinppm.Range:0-2000.
REG_DEMC_MODBUS_RH_VALUE
859WReg
Valuein%.Range:0-100.
REG_DEMC_MODBUS_CO2_OUT
860RReg
OutputofPIcontrollerforCO2regulation.
REG_DEMC_MODBUS_RH_OUT
861RReg
OutputofPIcontrollerforRHregulation.
REG_DEMC_ALLOWED
862RReg
Indicatesifautomodecanbeset(based
onsensordataanddemandcontrolset
points).
Bit0:
0:Automodecannotbeactivated
1:Automodecanbeactivated
Bit1-15:notused.
REG_DEMC_RH_SP_WINTER
863
R/W
RegRange:0–100
RegisterintroducedinPCU-EC4program
version5.09.00.
REG_DEMC_SUMMER_WIN-
TER_MODE
864RReg
0:Summer
1:Winter
RegisterintroducedinPCU-EC4program
version5.09.00.
REG_DEMC_SUMMER_WIN-
TER_CNTR_H
865RReg
Highest16bitsofremainingtimeuntil
summermode.
REG_DEMC_SUMMER_WIN-
TER_CNTR_H
866RReg
Lowest16bitsofremainingtimeuntil
summermode.
ModbusforResidentialunitsUserManual
D24810
16
SystemairSverigeAB