Modbus for residential D24810 User manual(A007)

7.3Registersforthedamper
NameRegister
address
RorR/W
NVMAccess
(Reg./Coil)
Description/remarks
REG_DAMPER_PWM
301RReg
Outputvalueforexchanger.0-100
correspondto0to10V .
7.4Registersfortherotor
NameRegister
address
RorR/W
NVMAccess
(Reg./Coil)
Description/remarks
REG_ROTOR_STATE
351RReg
Statefortherotorcontrolstatemachine.
0:Normal
1:Rotorfaultassumed
2:Rotorfaultdetected
3:Summermodeconditionsvalid,but
summermodenotyetactive.
4:Summermode
5:WaitingtogooutofManualsummer
modeduetotemperatureconditions
6:Manualsummermode
7:Rotorcleaningduringsummermode
8:Rotorcleaningduringmanualsummer
mode
9:Fansoff
10:Rotorcleaningduringfansoff
11:Rotorfault,conditionsforrotorfault
notvalidanymore
REG_ROTOR_RELAY_ACTIVE
352R
Reg+CoilCoil5617:rotorrelayactive.
0:notactive
1:active.
REG_SYSTEM_ROTOR_TYPE
353
R/W
Reg
Indicatesthetypeofrotorcontrol:
0:On/offcontrol
1:Variablecontrol
REG_SYSTEM_PASSIVE_HOUSE
354
R/W
Reg0:Passivehousemodenotactive
1:Passivehousemodeactive
RegisterintroducedinPCU-EC4program
version5.09.00
7.5RegistersforRHsensor
NameRegister
address
RorR/W
NVMAccess
(Reg./Coil)
Description/remarks
REG_RH_SENSOR_VALUE
381RReg
RHsensorvalue(in%).
Reserved
REG_RH_SENSOR_DATA_VALID
383RReg
IndicatesthatvaliddatafromtheRH
sensorisavailable.
ModbusforResidentialunitsUserManual
D24810
6
SystemairSverigeAB